2. DETAILS OF PARAMETER SETTING
(3) Alarm differential gap setting (AH1, AH2, AH3)
Set the alarm differential gap for each channel. In addition, they can be set simultaneously for all
channels.
Details of setting
Thermocouple
RTD
Voltage
Factory set value
0 (0.0) to span
Note 1
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage inputs:
0.2 % of span
(4) Alarm timer setting (ALT1, ALT2, ALT3)
Set the time until an alarm is actually output after being set to the alarm state.
Details of setting
Factory set value
0 to 6000 seconds
0
Setting is common to all channels.
The alarm timer function:
The alarm timer function regards the period until the alarm timer is set after measured value
(PV) or deviation exceeds the alarm set value as a non-alarm state and outputs an alarm after
the alarm timer setting time elapses.
The alarm timer starts being activated if the alarm is turned on. In addition, if the alarm state
is released while the alarm timer is being activated, no alarm is output.
Example: When set the alarm timer for 100 seconds
Measured value (PV)
Alarm set value
Set value (SV)
ON
Alarm output
Alarm timer
(100 seconds)
Alarm state
Alarm timer
(100 seconds)
Alarm state
When instrument specification is FAIL alarm, the alarm timer function does not operate.
28