Download WarmFlow COMBI 70 Technical information
Transcript
4 - BOILER INSTALLATION 4.5 Fit a low level balanced flue (square only) To fit a concentric (round) low level, high level or vertical balanced flue, refer to the instructions supplied with the kit. 1 Lift off the boiler case top panels. Remove and discard the appropriate blanking panel from the rear or side of the boiler casing as required. 2 Unpack the flue kit. 3 Place the circular fibre gasket into the boiler flue spigot. See Fig. 21. Fig. 23 6 Ensure that the flexible air tube hanging bracket is positioned correctly. See Fig. 24. 7 Turn the domed nut of the flue elbow clamp clockwise until the elbow is clamped to the boiler. Tighten the domed nut using a spanner. See Fig. 24. Fig. 21 4 Take the flue elbow and pass it through the hole in the boiler casing. Fit the flue elbow flange onto the boiler flue spigot ensuring that the clamp passes through the hole in the top of the boiler as shown in Figs. 22 and 23. 5 Ensure that the elbow is located centrally in the boiler spigot, and is facing in the required direction. Fig. 24 8 Extend the telescopic flue assembly to the approximate required length. Offer the flue assembly up to the flue elbow ensuring that the assembly is in line with the elbow and engage the flue pipe over the elbow. See Fig. 25. Holding the stainless steel terminal section of the kit, push the flue assembly together until the rectangular wall sleeve is just inside the boiler casing. Fig. 22 Fig. 25 Combi 70 & Combi 90 Oil Boilers 29