Download York YCSA Technical information

Transcript
Physical data, heat pump units
Characteristics
YCSA-H 120
T and TP
YCSA-H 150
T and TP
Cooling capacity
kW
114
145
Heating capacity
kW
119.6
150
Capacity control
%
25/50/75/100%
V/ph
400.3.50
Power supply
Compressor consumption in cooling
kW
4 x 10.2
4 x 11.8
Compressor consumption in heating
kW
4 x 9.25
4 x 12.5
Compressor amperage in cooling
A
4 x 18.2
4 x 21.4
Compressor amperage in heating
A
4 x 16.9
4 x 21.6
No. of refrigerant circuits
2
No. of compressors
2 TANDEM
Compressor type
Oil charge in litres
SCROLL
l
4 x 3.25
Oil type
POLYOL ESTER OIL
Heat exchanger
Nominal flow in cooling
4 x 4.14
PLATES
l/h
19 610
No. of fans
24 940
4
mm
630
710
Total fan consumption
W
4 x 600
4 x 860
Total fan amperage
A
4 x 2.75
4 x 3.9
36 000
48 000
Fan diameter
Total air flow
3
m /h
Refrigerant type
R-410A
Refrigerant charge
kg
2 x 20
2 x 29
Sound power level
dB (A)
86
88
Sound power level at 5 m.
dB (A)
64
66
Sound power level at 10 m.
dB (A)
58
60
Sound power level LN
dB (A)
82
84
Sound power level at 5 m. LN
dB (A)
60
62
Sound power level at 10 m. LN
dB (A)
54
56
Length
mm
3 416
3 770
Width
mm
Height
mm
Dimensions
8
1 101
2 190
2 263
Water connections, socket
2 1/2"
Water filter, socket