Safety information Product information Mechanical installation Electrical installation Getting started Basic Running the parameters motor Avoid placing sensitive signal circuits in a zone 300 mm (12 in) in the area immediately surrounding the power module. Figure 4-18 Sensitive signal circuit clearance Optimization NV Media Card Advanced parameters Technical Diagnostics data UL listing information NOTE 1 Ensure direct metal contact at the drive and filter mounting points. Any paint must be removed beforehand. The unbroken motor cable shield (unbroken) electrically connected to and held in place by means of the grounding bracket. Connect the shield of the motor cable to the ground terminal of the motor frame using a jumper that is as short as possible and not exceeding 50 mm (2 in) long. A complete 360° termination of the shield to the terminal housing of the motor is beneficial. From an EMC consideration it is irrelevant whether the motor cable contains an internal (safety) ground core, or if there is a separate external ground conductor, or where grounding is through the shield alone. An internal ground core will carry a high noise current and therefore it must be terminated as close as possible to the shield termination. ≥300 mm (12 in) Sensitive signal cable Figure 4-20 Grounding the motor cable shield Ensure good EMC grounding. Figure 4-19 Grounding the drive, motor cable shield and filter Unshielded wiring to the optional braking resistor(s) may be used provided the wiring runs internally to the enclosure. Ensure a minimum spacing of 300 mm (12 in) from the signal wiring and the AC supply wiring to the external EMC filter. If this condition cannot be met then the wiring must be shielded. 1 Unidrive M100 User Guide Issue Number: 1 45