Download Worcester R40HE Specifications
Transcript
Rectifying faults Error Fd Hot water has unpleasant odour or is dark colour (system boiler) Check Action This is generally caused by the formation of hydrogen sulphide by sulphate-reducing bacteria. Such bacteria are found in water which is very low in oxygen and live off the hydrogen produced by the anode. 1. B Clean the hot water cylinder. B Replace the sacrificial anode. B Heat cylinder to a temperature ≥60˚C 2. B Replace magnesium sacrificial anode with impressed-current anode. The conversion costs are payable by the operator! Text display fails to respond, no display or display incorrect Check Action Ignition lead is not fitted as specified in installation instructions (i.e. the lead should be routed through the clip on the underside of the air box). B Hook igniter lead over clip on underside of air box. -orB Route igniter lead behind gas valve. Condensation in the flue pipe 1. Check Action Is diaphragm in mixer unit fitted correctly (see installation instructions)? B Open mixer unit (29). B Check diaphragm for correct orientation, soiling and splitting. B Fit diaphragm as per installation instructions or replace. B Close mixer unit. 7 181 465 347 (05.01) 41