Table 3 — LID Screens (cont)
EXAMPLE 11 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
4. Press SELECT .
1. Press
MENU
5. Scroll down to highlight MAINT02.
.
6. Press SELECT .
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
DESCRIPTION
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP
Override Threshold
CONDENSER PRESSURE
Override Threshold
EVAPORATOR REFRIG TEMP
Override Threshold
DISCHARGE TEMPERATURE
Alert Threshold
OIL FILTER PRESSURE DROP
Alert Threshold
CONFIGURABLE RANGE
−40-245 (−40-118)
150-200 (66-93)
0-420 (0-2896)
150-250 (1034-1724)
−40-245 (−40-118)
2-45 (1-7.2)
−40-245 (−40-118)
170-200 (76.7-93.3)
0-120 (0-827)
15-90 (103-621)
UNITS
REFERENCE POINT NAME
DEG F (DEG
DEG F (DEG
PSI (kPa)
PSI (kPa)
DEG F (DEG
DEG F (DEG
DEG F (DEG
DEG F (DEG
PSID (kPad)
PSID (kPad)
C)
C)
C)
C)
C)
C)
DEFAULT VALUE
MTRW
mt over
CRP
cp over
ERT
rt over
CMPD
cd alert
oil fltr
oil alrt
200 (93)
230 (1586)
35 (1.7)
200 (93.3)
30 (207)
NOTES:
1. Overriding shall not be supported on this maintenance screen. Active overrides shall show the associated point in alert (!). Only values with capital
letter reference point names shall be variables available for read operation.
2. Values in [ ] indicate HFC-134a values.
EXAMPLE 12 — MAINTENANCE (MAINT03) DISPLAY SCREEN
To access this display from the LID default screen:
4. Press SELECT .
5. Scroll down to highlight MAINT03.
1. Press MENU .
6. Press SELECT .
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
DESCRIPTION
Hot Gas Bypass ACTIVE ?
Active Delta P
Active Delta T
Calculated Delta T
STATUS
NO/YES
0-200 (0-1379)
0-200 (0-111)
0-200 (0-111)
UNITS
REFERENCE POINT NAME
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
dp a
dt a
dt c
NOTE: Overriding shall not be supported on this maintenance screen. Active overrides shall show the associated point in alert (*). Only values with
capital letter reference point names shall be variables available for read operation.
EXAMPLE 13 — MAINTENANCE (MAINT04) DISPLAY SCREEN
To access this display from the LID default screen:
4. Press SELECT .
5. Scroll down to highlight MAINT04..
1. Press MENU .
6. Press SELECT .
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
DESCRIPTION
LEAD/LAG: Configuration
Current Mode
Load Balance Option
LAG Start Time
LAG Stop Time
Prestart Fault Time
Pulldown: Delta T/Min
Satisfied?
LEAD CHILLER in Control
LAG CHILLER: Mode
Run Status
Start/Stop
Recovery Start Request
STANDBY CHILLER: Mode
Run Status
Start/Stop
Recovery Start Request
STATUS
UNITS
DISABLE,LEAD,LAG,STANDBY
DISABLE,LEAD,LAG,STANDBY
DISABLE/ENABLE
0-99
MIN
0-99
MIN
0-30
MIN
x.xx
D DEG
0/1
NO/YES
0/1
NO/YES
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown
Stop,Start,Retain
No/Yes
Reset,Off,Local,CCN
Timeout,Recycle,Startup, Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown
Stop,Start,Retain
No/Yes
NOTES:
1. Overriding shall not be supported on this maintenance screen.
2. D =delta degrees.
28
REFERENCE POINT NAME
leadlag
llmode
loadbal
lagstart
lagstop
preflt
pull dt
pull sat
leadctrl
lagmode
lagstat
lag s s
lag rec
stdmode
stdstat
std
std
s s
rec