Download Samson 1400 Operating instructions
Transcript
Operation 8.2 Adjust the manual reference variable Operating modes 8.2.1 Automatic (AUTO) and manual (MAN) modes After initialization has been completed successfully, the positioner is in automatic mode (AUTO). Automatic mode % Switching to manual mode (MAN) % Turn → Code 1 Press , Code 1 blinks. Turn until sufficient pressure has been built up in the positioner and the control valve moves to the required position. Note: If no settings are entered within approx. two minutes, the positioner automatically returns to Code 0, but remains in manual mode. Switching to automatic mode Turn → Code 0 Press , display: AUtO, Code 0 blinks. Turn → MAN % Turn → Code 0 Press , Code 0 blinks. Turn → AUtO Press (AUTO): to switchover to automatic mode. Press to switchover to manual mode. The switchover is smooth since the manual mode starts up with the set point last used during automatic mode. The current position is displayed in %. EB 8387-3 EN 61