Download MTU 12 V 2000 P12 Operating instructions
Transcript
Alarm text Meaning 016 L2 P-LUBE OIL Lube-oil pressure too low (2nd limit) automatic engine shutdown Task 1. Check engine-oil level and top up, if required (→ Page 123); 2. Try to re-start the engine (→ Page 52). 3. Contact Service. 023 L1 COOLANT LEVEL Engine coolant level too low Check coolant level and top up, if re‐ quired (→ Page 131) . 024 L2 COOLANT LEVEL Engine coolant level too low Check coolant level and top up, if re‐ quired (→ Page 131). 030 ENGINE OVER‐ SPEED Engine overspeed; automatic engine shutdown 033 L1 P-FUELFIL‐ TER DIFF Differential pressure before/af‐ Replace fuel filter (→ Page 110). ter fuel filter too high 051 L1 T-LUBE OIL Lube-oil temperature too high (1st limit) 052 L2 T-LUBE OIL Lube-oil temperature too high (2nd limit) 067 L1 T-COOLANT Coolant temperature too high (1st limit) warning 068 L2 T-COOLANT Coolant temperature too high (2nd limit) automatic engine shutdown 1. Acknowledge alarm. 2. Try to re-start the engine (→ Page 52). 3. Contact Service. Reduce power. 1. Reduce power. 2. If fault occurs repeatedly: Contact Service. Reduce power. 1. Allow the engine to cool down. 2. Check coolant cooler (elements etc.) and clean contaminated parts (see manufacturer's documentation). 3. Re-start the engine (→ Page 52). 4. If fault occurs repeatedly: Contact Service. 069 L1 T-EXTERN 1 Violation of first limit for exter‐ (Depending on the corresponding meas‐ nal temperature channel 1 uring point, which is read via CAN bus) 070 L2 T-EXTERN 1 Violation of second limit for external temperature channel 1 071 L1 T-EXTERN 2 Violation of first limit for exter‐ (Depending on the corresponding meas‐ nal temperature channel 2 uring point, which is read via CAN bus) 072 L2 T-EXTERN 2 Violation of second limit for external temperature channel 2 073 L1 P-EXTERN 1 Violation of first limit for exter‐ (Depending on the corresponding meas‐ nal pressure channel 1 uring point, which is read via CAN bus) 074 L2 P-EXTERN 1 Violation of second limit for external pressure channel 1 075 L1 P-EXTERN 2 Violation of first limit for exter‐ (Depending on the corresponding meas‐ nal pressure channel 2 uring point, which is read via CAN bus) 076 L2 P-EXTERN 2 Violation of second limit for external pressure channel 2 (Depending on the corresponding meas‐ uring point, which is read via CAN bus) 077 LIM EXT.COOL‐ ANT LEV. Alarm from external coolant level monitoring (Depending on the corresponding meas‐ uring point, which is read via CAN bus) 74 | Troubleshooting | MS150025/02E 2012-10 (Depending on the corresponding meas‐ uring point, which is read via CAN bus) (Depending on the corresponding meas‐ uring point, which is read via CAN bus) (Depending on the corresponding meas‐ uring point, which is read via CAN bus) TIM-ID: 0000003157 - 001 Fault code