Alarm text
Meaning
016
L2 P-LUBE OIL
Lube-oil pressure too low (2nd
limit)
automatic engine shutdown
Task
1. Check engine-oil level and top up, if
required (→ Page 123);
2. Try to re-start the engine
(→ Page 52).
3. Contact Service.
023
L1 COOLANT
LEVEL
Engine coolant level too low
Check coolant level and top up, if re‐
quired (→ Page 131) .
024
L2 COOLANT
LEVEL
Engine coolant level too low
Check coolant level and top up, if re‐
quired (→ Page 131).
030
ENGINE OVER‐
SPEED
Engine overspeed; automatic
engine shutdown
033
L1 P-FUELFIL‐
TER DIFF
Differential pressure before/af‐ Replace fuel filter (→ Page 110).
ter fuel filter too high
051
L1 T-LUBE OIL
Lube-oil temperature too high
(1st limit)
052
L2 T-LUBE OIL
Lube-oil temperature too high
(2nd limit)
067
L1 T-COOLANT
Coolant temperature too high
(1st limit) warning
068
L2 T-COOLANT
Coolant temperature too high
(2nd limit)
automatic engine shutdown
1. Acknowledge alarm.
2. Try to re-start the engine
(→ Page 52).
3. Contact Service.
Reduce power.
1. Reduce power.
2. If fault occurs repeatedly: Contact
Service.
Reduce power.
1. Allow the engine to cool down.
2. Check coolant cooler (elements etc.)
and clean contaminated parts (see
manufacturer's documentation).
3. Re-start the engine (→ Page 52).
4. If fault occurs repeatedly: Contact
Service.
069
L1 T-EXTERN 1
Violation of first limit for exter‐ (Depending on the corresponding meas‐
nal temperature channel 1
uring point, which is read via CAN bus)
070
L2 T-EXTERN 1
Violation of second limit for
external temperature channel
1
071
L1 T-EXTERN 2
Violation of first limit for exter‐ (Depending on the corresponding meas‐
nal temperature channel 2
uring point, which is read via CAN bus)
072
L2 T-EXTERN 2
Violation of second limit for
external temperature channel
2
073
L1 P-EXTERN 1
Violation of first limit for exter‐ (Depending on the corresponding meas‐
nal pressure channel 1
uring point, which is read via CAN bus)
074
L2 P-EXTERN 1
Violation of second limit for
external pressure channel 1
075
L1 P-EXTERN 2
Violation of first limit for exter‐ (Depending on the corresponding meas‐
nal pressure channel 2
uring point, which is read via CAN bus)
076
L2 P-EXTERN 2
Violation of second limit for
external pressure channel 2
(Depending on the corresponding meas‐
uring point, which is read via CAN bus)
077
LIM EXT.COOL‐
ANT LEV.
Alarm from external coolant
level monitoring
(Depending on the corresponding meas‐
uring point, which is read via CAN bus)
74 | Troubleshooting | MS150025/02E 2012-10
(Depending on the corresponding meas‐
uring point, which is read via CAN bus)
(Depending on the corresponding meas‐
uring point, which is read via CAN bus)
(Depending on the corresponding meas‐
uring point, which is read via CAN bus)
TIM-ID: 0000003157 - 001
Fault