Troubleshooting
Boiler Connection
Vitodens 100-W, WB1B Installation & Service
(continued)
Check fixed high limit
If the burner control unit cannot be reset after a fault
shutdown (F2), even though the boiler water temperature
is below approx. 203°F (95°C), check the fixed high limit.
1. Pull the leads from fixed high limit A.
2. Check the continuity of the fixed high limit with
a multimeter.
3. Remove faulty fixed high limit.
4. Coat the replacement fixed high limit with heat
conducting paste and install.
5. To reset, refer to page 76.
Check flue gas temperature sensor
1. Pull the leads from flue gas temperature sensor A.
2. Check the sensor resistance and compare it with the
curve.
Temperature
80
5600 332 -06
Resistance in K
3. Replace the sensor in case of severe deviation.