Download Viessmann WB1B Series Technical data
Transcript
Troubleshooting Boiler Connection Vitodens 100-W, WB1B Installation & Service (continued) Check fixed high limit If the burner control unit cannot be reset after a fault shutdown (F2), even though the boiler water temperature is below approx. 203°F (95°C), check the fixed high limit. 1. Pull the leads from fixed high limit A. 2. Check the continuity of the fixed high limit with a multimeter. 3. Remove faulty fixed high limit. 4. Coat the replacement fixed high limit with heat conducting paste and install. 5. To reset, refer to page 76. Check flue gas temperature sensor 1. Pull the leads from flue gas temperature sensor A. 2. Check the sensor resistance and compare it with the curve. Temperature 80 5600 332 -06 Resistance in K 3. Replace the sensor in case of severe deviation.