Transcript
18 (HT) > (VT) See graph to determine the required vertical rise VT for the required horizontal run HT. Simple venting configurations. 19 REQUIRED VERTICAL RISE IN FEET VT 20 10 3 0 5 10 15 20 25 30 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and vT For vent configurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < 3 VT Formula 2: HT + VT < 40 FT Example: V1 = 1.5 FT V2 = 5 FT VT = V1 + V2 = 1.5 + 5 = 6.5 FT H1 = 1 FT H2 = 1 FT H3 = 10.75 FT HR = H1 + H2 + H3 = 1 + 1 + 10.75 = 12.75 FT HO = .03 (three 90° elbows + one 45° elbow - 90°) = .03 (270° + 45° - 90°) = 6.75 FT HT = HR + HO = 12.75 + 6.75 = 19.5 FT HT + VT = 19.5 + 6.5 = 26 FT Formula 1: HT < 3 VT 3 VT = 3 x 6.5 = 19.5 FT 19.5 = 19.5 V2 90° H2 45° V1 H3 H1 90° Formula 2: HT + VT < 40 FT 26 < 40 Since both formulas are met, this vent configuration is acceptable. 18.7 W415-0672 / C / 08.13.12 90°