Transcript
GOLD CGs-4E Gas-Fired Water Boiler — Boiler Manual 3d Piping — low temp systems Figure 10 Boiler-bypass piping Zoning with circulators Alternative to primary/secondary piping Figures 8 and 9) 1 Boiler isolation (balancing) valves 2 Flow/check valve 3 System or zone circulator 4 System temperature gauges 5 Zone valve 6 Drain valve 7 System temperature valves (see instructions to the left for adjusting valves) 8 Blend temperature gauge 9 Relief valve Part number 550-110-282/1108 Figure 11 (continued) Boiler-bypass piping Zoning with zone valves (Alternative to primary/secondary piping Figures 8 and 9) 10 Automatic air vent (with diaphragm-type expan- sion tank), or connect to tank fitting (closed-type expansion tank). DO NOT use an automatic air vent when using closed-type expansion tank. It would allow air to leave the system, causing waterlogging of the expansion tank. 11 Fill valve 12 Diaphragm-type or bladder-type expansion tank, if used (For closed-type expansion tank, pipe from top of air separator to tank fitting as in Figure 5, page 15.) 13 Air separator and automatic vent, if used (Note that the fill valve must always be connected to the expansion tank, regardless of location of expansion tank, circulator or air separator.) 21