5 Communications Data for Modbus
Address
Parameter name
Setting (monitor) value
2E14
Transfer Output Upper
Limit
H'FFFFF831 to H'0000270F (−1999 to 9999) *1
0E2A
2E15
Transfer Output Lower
Limit
H'FFFFF831 to H'0000270F (−1999 to 9999) *1
0E48
2E24
Extraction of Square Root
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
Four-byte
mode
Two-byte
mode
0E28
2E29
Travel Time
H'00000001 to H'000003E7 (1 to 999)
0E54
2E2A
Valve Completely Closed
Position
H'00000000 to H'0000270F (0 to 9999)
0E56
2E2B
Valve Completely Open
Position
H'00000000 to H'0000270F (0 to 9999)
0E58
2E2C
Potentiometer
Specification Setting
H'00000000 to H'00000005 (0 to 5)
0F00
2F00
Alarm 1 Type
H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm with standby sequence
H'00000006 (6): Upper-limit alarm with standby sequence
H'00000007 (7): Lower-limit alarm with standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with standby
sequence
H'0000000B (11): Absolute-value lower-limit alarm with standby
sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15): SP absolute-value lower-limit alarm
H'00000010 (16): MV absolute-value upper-limit alarm
H'00000011 (17): MV absolute-value lower-limit alarm
Initial setting
5-1 Variable Area (Setting Range) List
*1
0E52
Level
5
0F02
2F01
Alarm 1 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F04
2F02
Alarm 1 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F06
2F03
Alarm 2 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
0F08
2F04
Alarm 2 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F0A
2F05
Alarm 2 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F0C
2F06
Alarm 3 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
0F0E
2F07
Alarm 3 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F10
2F08
Alarm 3 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F12
2F09
Alarm 4 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
The setting (monitor) range depends on the transfer output type setting. Refer to Section 6 Parameters in the E5@C-T
Digital Temperature Controller User’s Manual (Cat. No. H185).
E5†C-T Digital Controllers Programmable Type Communications Manual (H186)