Suggested Minimum Service
Also refer to additional instructions packed with boiler.
Verify proper operation after servicing.
Annual service call by qualified service
technician to include:
1. Check burners and flueways; clean if
necessary. Refer to “Cleaning Boiler Heating
Surfaces” (this page) and “Clean Main
Burners” (page 35).
2. Visually inspect base insulation. See page 31.
3. Follow “To Place in Operation,” page 31.
4. Visually inspect pilot and main burner
flames. See page 32.
5. Visually inspect venting system.
See page 32.
6. Check operation of low water cutoff, if used,
and additional field-installed controls. Refer
to manufacturer's instructions.
7. Check that boiler area is free from combustible materials, gasoline and other flammable vapors and liquids.
8. Check for and remove any obstruction to
the flow of combustion or ventilation air.
9. Follow instructions on circulator to oil,
if oil lubricated. Over-oiling will damage
circulator. Water-lubricated circulators do
not need oiling.
10. Oil blower motor. Follow instructions on
blower motor. Do not use common household oils.
11. Check relief valve. Follow manufacturer's
instructions on relief valve tag.
12. Check for leaks in boiler and piping. If
found, repair at once.
Failure to repair leaks can
cause iron corrosion, leading to
section failure and leaks. Do not use
petroleum-based sealing or stop-leak
compounds in boiler systems. Severe
damage to boiler will occur, resulting in
severe personal injury, death or substantial
property damage.
13. Check automatic air vent for leakage. If
leaking, remove vent cap and push valve
core in to wash off accumulated sediment
on valve seat. Release valve, replace cap and
open one turn.
Shutdown procedure:
1. Follow “To Turn Off Gas to Appliance”
instructions on boiler.
2. Do not drain system unless it will be
exposed to freezing temperatures. If using
antifreeze in system do not drain.
34
Cleaning boiler heating surfaces:
•
POSSIBLE CANCER HAZARD BY
INHALATION
• CAN CAUSE RESPIRATORY, SKIN
AND EYE IRRITATION
This product contains fiberglass wool and ceramic
fiber materials. Airborne fibers from these materials
have been listed by the State of California as a
possible cause of cancer through inhalation. Apply
special care when handling ceramic fiber materials (chamber lining and base insulation). Ceramic
fibers can be converted to chrystobalites, a substance listed as a probable cause of cancer.
Suppliers of fiberglass wool products recommend
the following precautions be taken when handling
these materials.
Precautionary measures:
• Avoid breathing fiberglass dust and contact
with skin and eyes.
• Use NIOSH approved dust/mist respirator.
• Wear long-sleeved, loose fitting clothing, gloves
and eye protection.
• Wash work clothes separately from other
clothing. Rinse washer thoroughly.
• Operations such as sawing, blowing, tearout
and spraying may generate airborne fiber
concentration requiring additional protection.
First aid measures:
• Eye contact - Flush eyes with water to remove
dust. If symptoms persist, seek medical attention.
• Skin contact - Wash affected areas gently with
soap and warm water after handling.
1. Follow shutdown procedure.
2. Remove venting system connection to boiler.
3. Remove top jacket panel. Turn back
insulation.
4. Remove collector box/transition assembly.
Clean sealant from assembly and sections.
5. Remove radiation plates hanging between
sections.
6. Remove burners from base. Follow “Clean
Main Burners,” page 35.
7. Place newspapers in base of boiler to
collect soot.
8. Clean between sections with wire flue
brush.