5.6 Electrical output specifications when running on battery power
3 103 46 3 103 47 3 103 48 3 103 49 3 103 60 3 103 63 3 103 66 3 103 69 3 103 72
Nominal output
voltage
230 V ± 1%
Output
frequency
Nominal output
power VA
Active output power
with linear or
nonlinear load P.F. 0,7
Total harmonic
distortion of output
voltage
Overload
capacity
Tolerated power
factor range of
applied load
DC-AC conversion
efficiency with
linear load P.F. 1 and
charged batteries:
• with 50% load
• with 75% load
• with 100% load
50 Hz / 60Hz ± 1% (autosensing and/or as selected by operator)
1250VA
2500VA
3750VA
5000VA
5000VA
6250VA
7500VA
8750VA 10000VA
875W
1750W
2625W
3500W
3500W
4375W
5250W
6125W
7000W
< 1%
160% impusive
from 0,7 to 1
80%
80%
80%
ATTENTION:
There is a danger of explosion should the batteries be replaced with the wrong type.
Dispose of used batteries as per the instructions and precautions for their disposal on the battery label!
27
Operating and Maintenance Manual
UPS Megaline