DDC Controls Reset Start Point Field-adjustable from 0 to 10 psig (0 to 68.9 kPa) Main Air Pressure 15 to 30 psig (103 to 207 kPa) Air Consumption 28.8 scim (0.472 L/m) at 20 psig (138 kPa) main air pressure Operating Environment 40 to 120ºF (4 to 49°C) Storage Environment -40 to 140ºF (-40 to 60°C) Output Sensitivity 5 psig/0.02 in. wg (34.5 kPa/5.0 Pa) Physical Dimensions Width: 4.5" (114.3 mm) Length: 2.3" (58.4 mm) Height: 3.87" (98.3 mm) Weight: 11 oz (312 g) 3501 Pneumatic Volume Regulator Tubing Connections: 1/4" O.D. tubing connections The 3501 PVR can be set to control either normally open or normally-closed air valve actuators and can be calibrated to accept either direct-acting or reverse-acting thermostat signals. Fixed reset control of maximum and minimum airflow setpoints is provided.The controller is used primarily in dual-duct constant-volume applications because of its linear output response characteristics.The controller resets the primary air velocity linearly with a change in thermostat pressure. This is in contrast to the 3011 PVR, which resets velocity pressure with a change in thermostat pressure.This allows the 3501 PVR to have improved stability at low flows. Specifications Differential Pressure Range 0–1.0 in. wg (0–249 Pa) Minimum Setpoint Range 0–1.0 in. wg (0–249 Pa) Maximum Setpoint Range Minimum to 1.0 in. wg (249 Pa) Operating Static Pressure Range 0.25–6.0 in. wg (62.3–1494 Pa) VAV-PRC012-EN 189