Operation Thermostat signals are as follows: R 24VAC power to thermostat Y1 Call for compressor 1 or first stage cooling Y2 Call for compressor 2 or 2nd stage cooling G Call for supply fan W1 Call for heat 1 W2 Call for heat 2 Conventional thermostat – Gas/ Electric, Electric Heat: Function when Input/connection energized : G (fan) Fan runs continuously except during unoccupied mode (see next page) Y1 (compressor 1 Compressor #1 runs or economizer) or economizer operates Heat pump only: X2 Call for emergency heat O Switchover valve On = cooling, Off = heating T Bias for heat anticipation for those mechanical thermostats that use this function Y2 (compressor 2 Compressor #2 also or compressor 1 runs, or #1 while economizing) compressor runs while economizing W1 (gas / electric 1st stage heat heat first stage) W2 (gas / electric 2nd stage heat (if heat 2nd stage) available) Conventional thermostat – Heat Pump Function when Input/connection energized Cooling mode: G (fan) Fan runs continuously except during unoccupied mode (see next page) O (reversing valve Reversing valve in during cooling) cool mode Y1 + O Compressor #1 runs (first stage cooling) or economizer operates Y1 + Y2 + O Compressor #2 also (2nd stage cool) runs, or #1 compressor runs while economizing. Heating mode: G (fan) Fan runs continuously except during unoccupied mode (see below) Y1 (both Both compressors compressors 1st run stage heat) Y2 (during heating No change – nothing happens) W2 (electric heat 2nd stage) 2nd stage (electric) heat X2 (electric heat only) Electric heat only – no compressors T (provides heat anticipation signal for those mechanical thermostats that use this feature. If the thermostat used does not have a “T” terminal, disregard this terminal. RT-SVX19A-E4 45