Wiring
All wiring must conform to local and national electrical codes and ordinances.
Connect in accordance with the wiring diagrams provided by the equipment manufacturer.
This control has a single-pole, double-throw, snap-action
switch. The top left-hand terminal (red) is the common
terminal. The top right-hand terminal (blue) has an openon-rise switch action. The bottom center terminal (white)
has close-on-rise switch action.
RED
BLUE
OPEN ON RISE
OF TEMPERATURE
COMMON
WHITE
CLOSE ON RISE
OF TEMPERATURE
INSTALLATION AS AN OUTDOOR BULB
When used as a changeover control or outdoor thermostat, the bulb of this control should be located to measure
the actual outdoor air temperature. A mounting bracket is
provided for mounting the bulb.
ROOF
The mounting bracket should be fastened to some convenient outside part of the building that is shielded from the
direct rays of the sun, the direct fall of rain and snow, and
sufficiently above ground to keep it out of snow and ice.
The underside of the eaves or overhang of a NORTH or
NORTHEAST roof is a good location. It should be exposed to the circulation of air and wind.
CEILING
MOUNTING
BRACKET
OUTDOOR BULB
SETTING THE DIAL
The fixed indicator (B) points to temperature at which the
“R-B” contacts close and the “R-W” contacts open. Follow
these instructions to set the dial.
“B” FIXED INDICATOR
“A” ADJUSTING
SLOT
1. Insert a screwdriver in the adjusting slot (A) and turn
the dial until the fixed indicator (B) points to the lowest
temperature of the cycle.
2. Turn the differential adjusting screw (C) until the
moveable indicator (D) points to the highest temperature of the cycle.
“C” DIFFERENTIAL
ADJUSTING SCREW
“D” MOVABLE INDICATOR
2