Download Operating Instructions DMP 48 AS / DMP 48 AW

Transcript
Operating instructions DMP 48 AS / AW
DOLD GMBH
Sensor ID:
9.
Sensor
ID:
ID by ordering
key:
Sensor:
Max. display
range:
Max. setpoint
range:
Display:
P1
P2
P3
P4
P5
P1
P2
P3
P4
P5
Pt 100
Pt 100
Pt 100
Pt 100
Pt 100
-69...149°C
-69...249°C
-69...349°C
-69...699°C
-169...149°C
-50...100°C
-50...200°C
-50...300°C
-50...600°C
-150...100°C
3 digits
3 digits
3 digits
3 digits
4 digits
tL1
tL2
tn1
tn2
L1
L2
K1
K2
Fe-CuNi Type L
Fe-CuNi Type L
Ni Cr-Ni Type K
Ni Cr-Ni Type K
-24...499°C
-24...899°C
-24...649°C
-24...1299°C
0...450°C
0...850°C
0...600°C
0...1200°C
3 digi ts
3 digi ts
3 dig its
4 d igits
Line compensation, zero-point offset:
9.1 Line compensation:
Line compensation is required only with resistance thermometers in two-wire technology. Line
resistance can be counterbalanced with the "Cor" parameter (configuration level).
Proceed as follows to generate line compensation:
1.
2.
3.
4.
Connect a 100 Ω resistor to the end of the sensor line (corresponds to 0°C).
Read off the actual value from the display.
Jump to the configuration level.
Correct line resistance (display in °C) with the "Cor" parameter.
Example: 1. Displayed actual value:
2. "Cor" value to be set on the configuration level:
3. Confirm the set value with the P key.
Return to operating mode
4. Display of actual value:
5. Remove 100 Ω resistor from end of line.
+3.0°C
-3.0°C
0.0°C
9.2 Zero-point offset:
The "Cor" parameter can also be used for zero-point offset (offset value) towards plus or minus
(as in the above example).
DMP 48 AS
DMP 48 AW
Version:
033
Edition: 08.08.2006
Number of pages: 23 of 25
A0e033.doc