Transcript
Control functions Function descriptions 5.5.2 Summer compensation (PA5) The function is basically available for all systems with a cooling coil: System code numbers Anl 1 and Anl 4 to Anl 9. This summer compensation function lets the set points for supply air, exhaust air and room temperatures be shifted in a linear manner by means of two coordinates. For this purpose, the following parameters must be defined in PA5: Summer compensation when the outdoor temperature is greater: from this outdoor temperature onwards, the temperature set point is raised Set point at an outdoor temperature of 32 °C determines the gradient of the characteristic curve. 4 4 Example: In an air-conditioning system, the exhaust air temperature set point is be raised when the outdoor temperature is greater than 25 °C. At 32 °C, the exhaust air temperature set point should be 26 °C. Exhaust air temperature set point = 22 °C Summer compensation when the outdoor temperature is greater = 25 °C Set point at an outdoor temperature of 32 °C = 26 °C Supply air temperature maximum limit = 30 °C 4 4 4 4 5.5.3 Outdoor temperature-controlled supply air control The functionality of the summer compensation, see section 5.5.2, can also be used for an outdoor temperature-controlled supply air temperature control, e.g. with system code number Anl 0. The parameter Summer compensation when the outdoor temperature is greater (PA5) determines from which outdoor Set point °C temperature the Supply air temperature set point is to be reduced. The parameter Set point at an outdoor temperature of 32 °C (PA5) determines also the gradient of the characteristic curve (see also Fig. 25). Example: A heating coil is to warm up the supply air to 30 26 22 25 32 Outdoor temperature °C Fig. 24 ⋅ Summer compensation EB 5177 EN 71