B. Acyclic operation
If the measuring range is used to limit the value range of the
encoder to a value other than the specified singleturn resolution * 2x, the output position value is limited within the operating range. If rotation of the encoder shaft causes the position value to exceed the maximum value or fall below 0, the
encoder indicates the value of the measuring range. See figure below.
Example of acyclic scaling:
Measuring steps per revolution = 100
Total measuring range
= 5000 (number
of revolutions: 50)
Figure 10 Acyclic scaling
4.4.7 Velocity function
The velocity data can be accessed if class 2 32-bit + velocity
configuration is used. In this case the input data consists of
32-bit position data plus 16-bit signed velocity data. The velocity value is negative in counterclockwise direction if the code
sequence is set to clockwise. If the measured velocity is
greater than the value that can be preset for the selected
velocity unit, the value is set to 0x7FFF (32768) or 0x8000
(–32768) depending on the direction of shaft rotation.
Note:
If one of the time-based velocity units is used
and scaling is set for the encoder, the velocity calculation is based on the scaled position
value. Consequently, the accuracy of the velocity value depends on the scaling set for
the encoder.
25