Download User Manual, PowerFlex Digital DC Drive
Transcript
Chapter 1 Installation and Wiring Table 32 - I/O Terminal Block 2 Designations 11 12 13 14 15 16 17 18 19 20 No. 11 12 13 14 15 16 Signal Internal 0V (Gnd) Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input Common 17 18 19 Not Used 24V Supply Common +24V DC Supply 20 PE ground Description Factory Default – Max +30V, 15V/3.2 mA, 24V/5 mA, 2 “Stop/CF” and 30V/6.4 mA. 3 “Start” A digital input (1…8) must be configured for 11 “Jog” “Enable”. 1 “Enable” Important: When using the internal +24V – DC supply (terminal 19) for digital inputs 1…4, you must connect the digital input common (terminal 16) to the +24V supply common (terminal 18). – Common for the internal power supply. – Drive supplied control input power. – Max. +20-30V, 200 mA Note: The total current draw is the sum of encoder power, digital outputs and any other loads connected to terminal 19. PE ground to drive chassis. – Config. Parameter – 133 [Digital In1 Sel] 134 [Digital In2 Sel] 135 [Digital In3 Sel] 136 [Digital In4 Sel] – – – – – Table 33 - I/O Terminal Block 3 Designations 21 22 23 24 25 26 27 28 29 30 No. 21 22 23 24 25 26 27 28 29 30 Signal Analog Output 1 (+) Analog Output 1 (–) Analog Output 2 (+) Analog Output 2 (–) Digital Output Common Digital Output 1 Digital Output 2 Digital Output 3 Digital Output 4 +24VDC Supply Description Max. ±10V, 5 mA. Max. +30V, 50 mA Supply voltage for the digital outputs. Max. +30V DC, 80 mA. Important: When using the internal +24V DC supply (terminal 19) for digital outputs 1…4, you must connect the digital output common (terminal 25) to the +24V supply common (terminal 18). Factory Default Config. Parameter 12 “Motor Speed” 66 [Anlg Out1 Sel] 13 “Motor Curr” 67 [Anlg Out2 Sel] – 5 “Ready” 9 “Fault” 2 “Spd Thresh” 4 “CurrentLimit” – – 145 [Digital Out1 Sel] 146 [Digital Out2 Sel] 147 [Digital Out3 Sel] 148 [Digital Out4 Sel] – Table 34 - I/O Terminal Block 4 Designations 31 72 32 33 34 35 36 37 38 39 No. 31 32 33 34 35 Signal Digital Input 5 Digital Input 6 Digital Input 7 Digital Input 8 Digital Input Common 36 … 40 Not Used 40 Description Max +30V, 15V/3.2 mA, 24V/5 mA, and 30V/6.4 mA. A digital input (1…8) must be configured for “Enable”. Important: When using the internal +24V DC supply (terminal 19) for digital inputs 5…8, you must connect the digital input common (terminal 35) to the +24V supply common (terminal 18). Rockwell Automation Publication 20P-UM001H-EN-P - April 2011 Factory Default 17 “Speed Sel 1” 18 “Speed Sel 2” 19 “Speed Sel 3” 31 “Contactor” – Config. Parameter 137 [Digital In5 Sel] 138 [Digital In6 Sel] 139 [Digital In7 Sel] 140 [Digital In8 Sel] – – –