Download User Manual, PowerFlex Digital DC Drive

Transcript
Chapter 1
Installation and Wiring
Table 32 - I/O Terminal Block 2 Designations
11
12
13
14
15
16
17
18
19
20
No.
11
12
13
14
15
16
Signal
Internal 0V (Gnd)
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input Common
17
18
19
Not Used
24V Supply Common
+24V DC Supply
20
PE ground
Description
Factory Default
–
Max +30V, 15V/3.2 mA, 24V/5 mA,
2 “Stop/CF”
and 30V/6.4 mA.
3 “Start”
A digital input (1…8) must be configured for 11 “Jog”
“Enable”.
1 “Enable”
Important: When using the internal +24V
–
DC supply (terminal 19) for digital inputs
1…4, you must connect the digital input
common (terminal 16) to the +24V supply
common (terminal 18).
–
Common for the internal power supply.
–
Drive supplied control input power.
–
Max. +20-30V, 200 mA
Note: The total current draw is the sum of
encoder power, digital outputs and any other
loads connected to terminal 19.
PE ground to drive chassis.
–
Config. Parameter
–
133 [Digital In1 Sel]
134 [Digital In2 Sel]
135 [Digital In3 Sel]
136 [Digital In4 Sel]
–
–
–
–
–
Table 33 - I/O Terminal Block 3 Designations
21
22
23
24
25
26
27
28
29
30
No.
21
22
23
24
25
26
27
28
29
30
Signal
Analog Output 1 (+)
Analog Output 1 (–)
Analog Output 2 (+)
Analog Output 2 (–)
Digital Output Common
Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4
+24VDC Supply
Description
Max. ±10V, 5 mA.
Max. +30V, 50 mA
Supply voltage for the digital outputs.
Max. +30V DC, 80 mA.
Important: When using the internal +24V
DC supply (terminal 19) for digital outputs
1…4, you must connect the digital output
common (terminal 25) to the +24V supply
common (terminal 18).
Factory
Default
Config. Parameter
12 “Motor Speed” 66 [Anlg Out1 Sel]
13 “Motor Curr”
67 [Anlg Out2 Sel]
–
5 “Ready”
9 “Fault”
2 “Spd Thresh”
4 “CurrentLimit”
–
–
145 [Digital Out1 Sel]
146 [Digital Out2 Sel]
147 [Digital Out3 Sel]
148 [Digital Out4 Sel]
–
Table 34 - I/O Terminal Block 4 Designations
31
72
32
33
34
35
36
37
38
39
No.
31
32
33
34
35
Signal
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
Digital Input Common
36
…
40
Not Used
40
Description
Max +30V, 15V/3.2 mA, 24V/5 mA,
and 30V/6.4 mA.
A digital input (1…8) must be configured for
“Enable”.
Important: When using the internal +24V
DC supply (terminal 19) for digital inputs
5…8, you must connect the digital input
common (terminal 35) to the +24V supply
common (terminal 18).
Rockwell Automation Publication 20P-UM001H-EN-P - April 2011
Factory Default
17 “Speed Sel 1”
18 “Speed Sel 2”
19 “Speed Sel 3”
31 “Contactor”
–
Config. Parameter
137 [Digital In5 Sel]
138 [Digital In6 Sel]
139 [Digital In7 Sel]
140 [Digital In8 Sel]
–
–
–