6 Hysteresis:
The hysteresis keeps the switching
P
state of the output stable if the
system pressure varies about the
SP
preset value. When the system
hysteresis
pressure is rising, the output
rP
switches when the switch-on
point has been reached (SPx);
t
1
when the system pressure is
0
Hno
falling again, the output switches
1
Hnc
back when the switch-off point
0
(rPx) has been reached.
The hysteresis can be set: First the switch-on point is set, then the
switch-off point with the requested difference.
Window function:
The window function enables
acceptable range
the monitoring of a defined
P
acceptable range. When the system pressure varies between the
SP
switch-on point (Sx1) and the
rP
switch-off point (rPx), the output
is switched (window function /
t
NO) or not switched (window
1
0
function / NC).
Fno
1
The width of the window can be
Fnc
0
set by means of the difference
between SPx and rPx. SPx = upper value, rPx = lower value.