Transcript
NI 9403
The vendor configuration extensions for the NI 9403 are listed in Table 87.
Table 87. NI 9403 Vendor Configuration Extension
Index
Sub
Type
R/W
0x2001
0
U32
R/W
Description
I/O direction control, default = 0
NI 9403 Direction Control
The direction control field has one bit for each I/O pin, with bit 0 matching
channel 0, and so forth. 0 in the direction control indicates that I/O is an
input; 1 indicates an output.
Both the input and output data is transmitted in the PDO regardless of the direction
control; only the relevant bits are connected to the I/O pins.
Note
NI 9476
The vendor configuration extensions for the NI 9476 are listed in Table 88.
Table 88. NI 9476 Vendor Configuration Extensions
Index
Sub
Type
R/W
0x2002
0
U32
R
Description
Error Status, sent as 8-bit PDO
NI 9476 Error Status
If a channel over-current occurs on any of the 32 channels, the
corresponding bit in error status field is set to inform the user.
Errors are automatically internally acknowledged on the cycle after the
error is reported.