Download Movifit-MC - Operating Instructions
Transcript
I 6 Startup MOVIFIT® MC startup 0 6.4.2 Startup with PROFINET IO, EtherNet/IP, or Modbus/TCP 1. Check the MOVIFIT® connection. TIP In conjunction with PROFINET IO, EtherNet/IP or Modbus/TCP, you do not have to make any settings on the MOVIFIT® for fieldbus startup. The entire startup is carried out using software tools and is described in the applicable manuals: • "MOVIFIT® Function Level Classic..." manual1) • "MOVIFIT® Function Level Technology..." manual1) 1) The "MOVIFIT® Function Level Classic" and "MOVIFIT® Function Level Technology" manuals are available in several fieldbus-specific versions. 2. Set DIP switch S11/2 "DEFIP" to "ON". DIP switch S11/2 = ON ® MOVIFIT function level "Technology" MOVIFIT® function level "Classic" DHCP 2 DEF IP DEF IP 1 3 res. (OFF) ON 4 res. (OFF) 2 S11 1 ON S11 res. (OFF) 1167697803 1167754379 This sets the address parameters to the following default values: IP address: 192.168.10.4 Subnet mask: 255.255.255.0 Gateway: 0.0.0.0 3. Mount the MOVIFIT® EBOX on the ABOX and close it. 4. Switch on the 24V_C and 24V_S supply voltage(s). The associated control LEDs should now light up green. 96 Operating Instructions – MOVIFIT®-FC