Download Movifit-MC - Operating Instructions

Transcript
I
6
Startup
MOVIFIT® MC startup
0
6.4.2
Startup with PROFINET IO, EtherNet/IP, or Modbus/TCP
1. Check the MOVIFIT® connection.
TIP
In conjunction with PROFINET IO, EtherNet/IP or Modbus/TCP, you do not have to
make any settings on the MOVIFIT® for fieldbus startup. The entire startup is carried
out using software tools and is described in the applicable manuals:
•
"MOVIFIT® Function Level Classic..." manual1)
•
"MOVIFIT® Function Level Technology..." manual1)
1) The "MOVIFIT® Function Level Classic" and "MOVIFIT® Function Level Technology" manuals are available in several fieldbus-specific
versions.
2. Set DIP switch S11/2 "DEFIP" to "ON".
DIP switch S11/2 = ON
®
MOVIFIT function level "Technology"
MOVIFIT® function level "Classic"
DHCP
2
DEF IP
DEF IP
1
3
res. (OFF)
ON
4
res. (OFF)
2
S11
1
ON
S11
res. (OFF)
1167697803
1167754379
This sets the address parameters to the following default values:
IP address:
192.168.10.4
Subnet mask:
255.255.255.0
Gateway:
0.0.0.0
3. Mount the MOVIFIT® EBOX on the ABOX and close it.
4. Switch on the 24V_C and 24V_S supply voltage(s). The associated control LEDs
should now light up green.
96
Operating Instructions – MOVIFIT®-FC