Transcript
Avvertenza: Eseguita la taratura alla massima potenza, si deve ricontrollare quella della minima, in quanto potrebbe essere stata influenzata dalla taratura della massima; se necessario ripetere le operazioni descritte in “Taratura del bruciatore alla minima potenza”. A questo punto, ripristinare il funzionamento automatico del bruciatore premendo il tasto 4 (PRG) di Fig. 6.3.4.1. Per il controllo della corretta posizione degli elettrodi del bruciatore vedere “Pulizia del bruciatore”. Fig. 6.4.1 Warning: Once the calibration at maximum output has been performed, check the minimum calibration again, as it may have been affected by the maximum calibration; if necessary, repeat the operations described in Calibrating the burner at minimum output. At this point, restart the automatic operation of the burner by pressing button 4 (PRG), as shown in Fig. 6.3.4.1. To check the correct position of the burner electrodes, see Cleaning the burner. 6.4 Arresto 6.4 Shut-down In occasione della sosta stagionale oppure per manutenzione sulle parti elettriche e/o idrauliche, è opportuno porre l’umidificatore fuori servizio. Seguire le seguenti istruzioni: • premere l’interruttore on/off posizionandolo su 0 (vedi Fig. 6.4.1. ) e verificando che il display del controllore sia spento; • aprire il sezionatore di linea d'alimentazione all’umidificatore; • chiudere il rubinetto d’intercettazione del gas e dell’acqua all'umidificatore. Se in occasione dell'arresto si desidera vuotare il bollitore, prima di togliere l’alimentazione all’unità, premere il pulsante 4 di drain (vedi Fig. 6.3.1.), attivando l’elettropompa di drenaggio e mantenerlo manualmente in tale posizione fino al completo svuotamento dall’acqua. Il livello dell’acqua è visibile attraverso l’involucro del controllo di livello e del sottostante tubo di collegamento al bollitore. In caso di malfunzionamento dell’elettropompa di drenaggio è possibile vuotare il bollitore manualmente aprendo il rubinetto (con tappo di sicurezza) posto alla base del bollitore dopo aver collegato un’opportuna tubazione di scarico. In occasione della sosta stagionale si consiglia di svuotare completamente il bollitore e pulirlo dalle eventuali incrostazioni interne. During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the plumbing, the humidifier should be placed out-of-service. Follow the instructions below: • move the ON/OFF switch to 0 (see Fig. 6.4.1.) and check that the display on the controller is off; • open the mains power switch to the humidifier; • close the gas and water shut-off taps. If during a shut-down the boiler needs to be emptied, before disconnecting power from the unit press the drain button 4 (see Fig. 6.3.1) to start the drain pump, and hold it manually in this position until the water has been completely emptied. The level of the water can be seen through the cover on the level control and the connection pipe to the lower manifold, where the boiler is positioned. In the event of malfunction of the drain pump, the boiler can be emptied manually, by opening the tap (with safety cap) fitted at the base of the boiler, after having connected a suitable drain pipe. During seasonal shut-down the boiler should be emptied completely and cleaned for any deposits. L’operazione di svuotamento del bollitore può essere effettuata anche agendo sul pannello di controllo come segue: • spegnere l’unità agendo sull’interruttore ON/OFF (vedi Fig. 6.3.1); • riaccendere nuovamente l’unità; • entro i primi 5 secondi dall’accensione premere contemporaneamente i tasti e ; • dopo 2 secondi viene attivata l’elettropompa di drenaggio per un periodo di circa 5 minuti, al termine del quale l’umidificatore viene di nuovo avviato come precedentemente descritto nel capitolo” avviamento ed arresto”. Durante lo scarico il controllo mostra il simbolo “-dr” (drain) (vedi Fig. 6.4.2). dehum. The boiler can also be emptied using the control panel, as follows: • turn the unit off using the ON/OFF switch (see Fig. 6.3.1); • turn the unit on again; • within 5 sec from start-up, press the and buttons together; • after 2 seconds, the drain pump starts for around 5 minutes, at the end of the which the humidifier is started again as described above in the chapter “start-up and shut-down”. During the drain phase, the controller shows the symbol “-dr” (drain) (see Fig. 6.4.2). x1000 PRG reset SEL alarm Fig. 6.4.2 25 gaSteam cod. +030221930 rel. 5.3 - 06.06.2005