Download User Guide - Honeywell
Transcript
DT92E ENERGY SAVING ECO FEATURE How to Exit ECO Mode To exit ECO mode, simply press the green ECO button again. ECO will disappear from the display and the thermostat will control to its previous set temperature. FINE TUNING YOUR DT92E Changing the DT92E Installer Parameters The DT92E has a special Installer Mode where some features can be adjusted to suit your lifestyle or preferences – these are called Installer Parameters, and are listed in the table below, along with a description of the options that are possible. Your installer should set this up for you to suit your application (see CONFIGURATION & SERVICE DATA section). However, you may wish to alter some of the settings yourself, and this section shows you how to do this. INSTALLER PARAMETER Parameter Default Value Options Description Offset to measured temperature Temperature measurement offset t0 0 -3 to 3 K Upper setpoint limit uL 35 21 to 35°C Lower setpoint limit LL 5 5 to 21°C Lower set temperature limit in °C Energy saving ECO setpoint ES 18 5 to 35°C Energy saving ECO set temperature in °C Reset parameters to factory settings FS 1 0, 1 Upper set temperature limit in °C Parameter will be set to 0 if any of the other parameter values have been changed. Set to 1 to get back to factory settings. 23