Download CPC400 Series User's Guide
Transcript
CPC400 Series User’s Guide Chapter 2: Installation TB50 or TB18 Solid-State Relay Solid-State Relay - + - + Solid-State Relay - + Heat Output Cool Output Alarm Output +5VÅ (ac) Figure 2.22 Sample Heat, Cool and Alarm Output Connections TB50 or TB18 Heat Output Cool Output Alarm Output Common Solid-State Relay Solid-State Relay - - + + Solid-State Relay - + - PS + Figure 2.23 Output Connections Using External Power Supply CPU Watchdog Timer The CPU watchdog timer constantly monitors the microprocessor. It is a sink output located on TB50 terminal 6 or TB18 terminal 3. The output can be connected to an external circuit or device to monitor whether the controller is powered and operational. Do not exceed the 5VÎ (dc), 10 mAdc rating for the watchdog output. The output is on (low) when the microprocessor is operating; when it stops operating, the output goes off (high). Figure 2.24 and Figure 2.25 show the recommended circuit for the watchdog timer output for the TB50 and the TB18. TB50 + 5VÎ (dc) (Terminal 1) Watchdog Timer (Terminal 6) + Solid-State Relay - Figure 2.24 TB50 Watchdog Timer Output TB18 + 5VÎ (dc) (Terminal 1) Watchdog Timer (Terminal 3) + Solid-State Relay - Figure 2.25 TB18 Watchdog Timer Output Doc. 0600-2900-2000 Watlow Anafaze 35