Download technical & service manual dc inverter split system air conditioner

Transcript
Indoor Unit
Outdoor Unit
SAP-KRV124EHDX
SAP-CRV124EHDX
Power Source
220 to 240V Single-Phase 50Hz
Voltage Rating
230 V
Performance
Capacity
Air Circulation (High)
Moisture Removal (High)
Electrical Rating
Available Voltage Range
Running Amperes
Power Input
Power Factor
E.E.R.
C.O.P.
Compressor Locked Rotor Amperes
Features
Controls / Temperature Control
Control Unit
Timer
Fan Speeds
Airflow Direction (Indoor)
Height
Width
Depth
Package Dimensions Height
Width
Depth
Weight
Net
Shipping
Shipping Volume
Heating
4.80 ( 0.9 to 6.0 )
16,400 ( 3,100 to 20,500 )
630
-
Cooling
V
A
W
%
W/W
W/W
A
4.00
875
Heating
198 to 264
( 1.6 to 7.8 )
5.20 ( 1.6 to 9.9 )
( 250 to 1,435 )
1,140 ( 250 to 1,545 )
95
95
4.0
4.21
7.8
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
24-Hour ON or OFF Timer, 1.2.3.5-Hours OFF Timer
Auto and 3 steps
Auto
Auto
Washable, Anti-Mold
DC Twin Rotary (Inverter)
R410A / 1,380
Electric Expansion Valve
40 / 38 / 30 / 22
41 / 38 / 30 / 22
50
51
Flare Type
7.5
6.35 (1/4)
9.52 (3/8)
Optional / Air Clean Filter
Indoor / Outdoor
Horizontal
Vertical
Air Filter
Compressor
Refrigerant / Amount charged at shipment
Refrigerant Control
Operation Sound
Indoor : Hi/Me/Lo/Qt*
(*Qt = Quiet mode)
Outdoor : Hi
Refrigerant Tubing Connections
Max. allowable tubing length at shipment
Refrigerant
Narrow tube
Tube Diameter
Wide tube
Refrigerant Tube Kit / Accessories
Dimensions & Weight
Unit Dimensions
Cooling
3.50 ( 0.9 to 4.2 )
11,900 ( 3,100 to 14,300 )
630
2.0
kW
BTU/h
m 3/h
Liters/h
g
dB-A
dB-A
m
mm (in.)
mm (in.)
Indoor Unit
300
898
200
280
970
360
12.5
14.0
0.098
mm
mm
mm
mm
mm
mm
kg
kg
m3
Outdoor Unit
569
790
285
645
921
386
40.0
43.0
0.229
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature
Outdoor air temperature
Heating: Indoor air temperature
Outdoor air temperature
27°C D.B. / 19°C W.B.
35°C D.B. / 24°C W.B.
20°C D.B.
7°C D.B. / 6°C W.B.
7