Download Operating Instructions Fire Alarm System EBL128
Transcript
Panasonic Eco Solutions Nordic AB MEW01623 Rev: - EBL128 Operating Instructions V2.0.x calibrated via menu H5/A1. Some external influence has caused a fault in the SSW. This is very serious. Call for service personnel/engineer. FAULT: Restart, code xx addr yyyyyyyyyyy C.i.e. (EBL128) restart has occurred. See also page 77. xx=00: Power up Restart. (Power supply connected) xx=01: Watchdog Reset. xx=02: Accidental jump to reset vector. xx=03: Restart after Software download xx=04-19: Unexpected interrupt. xx=20: S/W monitoring fault xx=25: Restart after SSD download NOTE! xx=00, 03 and 25 are normal. Only acknowledge the "fault". xx=01, 02 or 04-20 appearing often: call for service personnel / engineer. yy…y = memory address (before restart). Write down the address and inform the service personnel/engineer. FAULT: Sensor zz-aa Press "" to see the technical address. FAULT: Sensor techn address xxx zz-aa = Zone-Address. xxx = COM loop address. The communication with the sensor / detector is not all right, i.e. the unit is out of order / faulty. For detector types 33xx / 43xx / 44xx: The built-in self verification function has reported a fault status. FAULT: Several faults on COM-loop Breaks (cut-offs) / short-circuits in more than one segment on the COM loop. Normally this fault is generated in conjunction with some cut-off faults / short-circuit faults. In that case, first correct one fault and the next fault will be presented. FAULT: Short-circuit, internal COM-loop Short-circuit on the connection (ribbon cable) to or between the expansion boards (458x) in the c.i.e. (EBL128). 67