Lineagrafica
280 BATT
WARNINGS
- It is recommended to keep to the instructions here outlined - check the specifications on the motor sticker with your mains
supply.
- Dispose properly of the packaging: cardboard, nylon, polystyrene, through specializing companies.
- Should the operator be removed, do not cut the electric cable. This must be properly removed from the terminal board in the
junction box.
- Switch off the mains switch before removing the junction box cover where the electric cable of APROLI 280 BATT is terminated.
- All the system must be earthed by using the yellow/green wire, marked by its specific symbol.
- It is recommended to read the regulations, suggestions and remarks quoted in the booklet "Warnings".
- Should APROLI 280 BATT be removed for maintenance, servicing or repair, tighten the air bleeding screw to prevent oil coming
out of the reservoir during transport.
Meccanica Fadini recommends the control panel ELPRO 13 CEI to
achieve an installation that is in conformity to the existing safety
standards.
The electronic programmer ELPRO 13 incorporates and can provide
all the functions which are required by the most demanding
applications with swinging gates.
In addition to the standard features of a conventional control box
type ELPRO 9 (see page 8 pic. 13) the following requirements can
be provided: “stroke reversing pulse”, pedestrian mode, stop in any
gate position by holding down the remote control button. Among
the added features and improvements of ELPRO 13 in conformity to
the European safety standards, there is the mains rotary switch: it
is fitted to the box cover and switches off the mains voltage whenever
the cover is removed.
3-2003
APROLI
STATIC GATE WEIGHT
400 Kg each leaf
13 CEI
SINGLE-PHASE
l apricancel lo
CUT OFF MAINS SWITCH
The “CE” mark certifies that the operator conforms to the essential
requirements of the European Directive art. 10 EEC 73/23, in relation
to the manufacturer’s declaration for the supplied items, in
compliance with the body of the regulations ISO 9000= UNI EN 29000.
Automation in conformity to EN 12453, EN 12445 safety standard.
The growth of MECCANICA FADINI has always been based
on the development of guaranteed products thanks to our
“TOTAL QUALITY CONTROL” system which ensures constant
quality standards, updated knowledge of the European
Standards and compliance with their requirements, in view
of an ever increasing process of improvement.
EUROPEAN MARK CERTIFYING CONFORMITY
TO THE ESSENTIAL REQUIREMENTS OF THE
STANDARDS 98/37 EC
• DECLARATION OF CONFORMITY
• GENERAL WARNINGS
• EN 12453, EN 12445 STANDARDS
• CEI EN 60204-1 STANDARDS
• WARRANTY CERTIFICATE ON THE CUSTOMER’S REQUEST
®
Made in Italy
GB
®
s.n.c.
AUTOMATIC GATE MANUFACTURERS
Distributor’s box
The manufacturers reserve the right to change the products without any previous notice
Via Mantova, 177/A - 37053 Cerea (Verona) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054 - e-mail: info@fadini.net - www.fadini.net
INSTALLATION MANUAL
®
APROLI
280 BATT
CUTAWAY VIEW OF THE ELECTRIC MOTOR ASSEMBLY
AND HYDRAULIC JACK
AVAILABLE TYPES: NON LOCKING - LOCKING - WITH FLOW REGULATOR
INSTRUCTIONS FOR THE INSTALLATION OF APROLI 280 BATT TO SWINGING
DOUBLE GATES WITH VERY LARGE PILLARS
it is recommended to follow these instructions to achieve a perfect application of the operator.
BASE AND
FIXING BRACKET
STUD
BOLT
ASSEMBLY ELEC.
MOTOR HYDR. JACK
PROTECTION
COVER
FIXING
SCREWS
TWO-WAY LOCKING
VALVE ASSEMBLY
PRESSURE SAFETY
VALVE “CLOSE”
GREEN
PRESSURE SAFETY
VALVE “OPEN”
RED
OIL RESERVOIR
TERMINAL PLUG
COVER
“C” “A”
TERMINAL PLUG
EARTH WIRE
OIL RESERVOIR
REAR CAP
0.25 HP
ELECTRIC MOTOR
HYDRAULIC LOBE
PUMP
JACK END CAP
1st PISTON
Lh
RACK
“B”
RELEASE LEVER
PISTON LINER
OPEN STOP ASSEMBLY
14 E22 NUT, STUD BOLT,
ADJUSTER COVER.
LEFT-HAND WASHER Ø 8.5
8M E13 NUT
RETAINING
DRIVING BENDED ARM
GRUB SCREW BENDED PLUG PROFILE
ARM
BOLT AND
NUT
STRAIGHT
ARM COVER
BUSH
STRAIGHT
ARM.
ADJUSTABLE
FIXING
SHOE
ARTICULATED ARM
LEFT-HANDED
SHAFT SUPPORT
SQUARE INDENTED
SHAFT
SCREW FOR
ADJUSTMENT
PIC. 2
2nd PISTON
PISTON LINER
MAIN ASSEMBLY
BLOCK WITH MOTOR
AND HYDR. JACK
First loosen the fastening screws to remove the cover. To do this, open the hinged door with the supplied key; one of the two fastening
screws is there. After the removal of the cover, the electro-hydraulic assembly is fully exposed, ie. “electric motor/hydraulic jack” fitted
with the pressure safety valves that control the thrust/pushing power of the operator and the emergency release in events like power
failure. It also includes a bracket, designed to provide fixing facility to a wall or pillar and a suitable outlet for the cables; an articulated
arm, adjustable to meet the most various distance requirements on site applications; and a shoe bracket to be fixed to the gate. The
operator is supplied already pre-filled with special oil to suit both high and low environment temperatures. It allows the correct
performance of APROLI 280 BATT within a temperature range from –20°C to +80°C. APROLI 280 BATT is produced and tested in the
workshops of MECCANICA FADINI which guarantees the long lasting reliability of this product in time.
PIC. 1
2
3
APROLI
280 BATT
CUTAWAY VIEW OF THE ELECTRIC MOTOR ASSEMBLY
AND HYDRAULIC JACK
AVAILABLE TYPES: NON LOCKING - LOCKING - WITH FLOW REGULATOR
INSTRUCTIONS FOR THE INSTALLATION OF APROLI 280 BATT TO SWINGING
DOUBLE GATES WITH VERY LARGE PILLARS
it is recommended to follow these instructions to achieve a perfect application of the operator.
BASE AND
FIXING BRACKET
STUD
BOLT
ASSEMBLY ELEC.
MOTOR HYDR. JACK
PROTECTION
COVER
FIXING
SCREWS
TWO-WAY LOCKING
VALVE ASSEMBLY
PRESSURE SAFETY
VALVE “CLOSE”
GREEN
PRESSURE SAFETY
VALVE “OPEN”
RED
OIL RESERVOIR
TERMINAL PLUG
COVER
“C” “A”
TERMINAL PLUG
EARTH WIRE
OIL RESERVOIR
REAR CAP
0.25 HP
ELECTRIC MOTOR
HYDRAULIC LOBE
PUMP
JACK END CAP
1st PISTON
Lh
RACK
“B”
RELEASE LEVER
PISTON LINER
OPEN STOP ASSEMBLY
14 E22 NUT, STUD BOLT,
ADJUSTER COVER.
LEFT-HAND WASHER Ø 8.5
8M E13 NUT
RETAINING
DRIVING BENDED ARM
GRUB SCREW BENDED PLUG PROFILE
ARM
BOLT AND
NUT
STRAIGHT
ARM COVER
BUSH
STRAIGHT
ARM.
ADJUSTABLE
FIXING
SHOE
ARTICULATED ARM
LEFT-HANDED
SHAFT SUPPORT
SQUARE INDENTED
SHAFT
SCREW FOR
ADJUSTMENT
PIC. 2
2nd PISTON
PISTON LINER
MAIN ASSEMBLY
BLOCK WITH MOTOR
AND HYDR. JACK
First loosen the fastening screws to remove the cover. To do this, open the hinged door with the supplied key; one of the two fastening
screws is there. After the removal of the cover, the electro-hydraulic assembly is fully exposed, ie. “electric motor/hydraulic jack” fitted
with the pressure safety valves that control the thrust/pushing power of the operator and the emergency release in events like power
failure. It also includes a bracket, designed to provide fixing facility to a wall or pillar and a suitable outlet for the cables; an articulated
arm, adjustable to meet the most various distance requirements on site applications; and a shoe bracket to be fixed to the gate. The
operator is supplied already pre-filled with special oil to suit both high and low environment temperatures. It allows the correct
performance of APROLI 280 BATT within a temperature range from –20°C to +80°C. APROLI 280 BATT is produced and tested in the
workshops of MECCANICA FADINI which guarantees the long lasting reliability of this product in time.
PIC. 1
2
3
HOW TO FIX APROLI 280 BATT TO A PILLAR BY EXPANDING BOLTS OR SCREWS
Before fitting the operator APROLI 280 BATT to the gate, make sure that the gate structure is adequate to be electrically operated and
that is strong enough to bear the mechanical stress of automatic operations and is well built and smooth running.
It is recommended to reinforce the gate and fix the metallic parts which may not work properly, do the necessary to prevent or correct
friction of the gate against the pavement or pillar (this must particularly apply to the gate hinges).
APPLICATION OF TWO APROLI 280 BATT ON TO A DOUBLE SWINGING GATE.
90° OPENING.
The recommended maximum gate width with APROLI 280 is 5 m. The locking type operator is recommended up to 2 m gate width. Beyond
2 m a lock is required to be fitted to the gate and the non locking type operator is advisable.
2m
VERY LARGE PILLAR
WHERE THE GATE
HINGE IS FIXED
IN THE MIDDLE
2m
LEFT-HAND
ARTICULATED
ARM
RIGHT-HAND
ARTICULATED
ARM
4 EXPANDING
BOLTS
MAINS SUPPLY
ELECTRIC CABLE
LEFT-HAND
GATE STOP IN
OPEN GATE
POSITION
90°
GATE STOP
IN CLOSE GATE
POSITION
RIGHT-HAND
GATE STOP IN
OPEN GATE
POSITION
90°
FIXING
BRACKET
NUTS WITH
WASHER
It is recommended that suitable gate stops are always fitted to
the system both in open and close gate positions. The gate stop
for open gate position is incorporated with the operator, both
right-hand and left-hand. The gate stop covers are different being
designed as handed units (part No. 2062=right-hand, 2055=left
hand). Another feature of the incorporated open gate stop is the
possibility of being adjusted to the required distance to achieve
the required opening angle, either 90° or more/less.
PIC. 5
GATE LEAF
OVERTURN
LEVEL
ARTICULATED
ARM
OPERATOR
COVER
PIC. 3
Rh
Fix the bracket to the pillar and bring the electric cable to the most suitable position so that the fixing of the articulated arm is allowed
to coincide with a solid crossing bar of the gate leaf. The shoe bracket is to be bolted or welded to the gate at a suitable distance which
is set after the first manual tests. (Release lever B page 10)
BOTH
Rh AND Lh
Lh
DISTANCE
The distance from gate pivot center to arm bolt
center is to be calculated through manual
operations of the gate before fixing the shoe
bracket. The distances on page 6-7 are merely
an application example.
RIGHT-HAND
ARTICULATED
ARM
LEFT-HAND
ARTICULATED
ARM
GRUB
SCREW
GRUB
SCREW
SQUARE
SECTION
SHAFT
COMPLETELY INSTALLED
UNIT. LEFT-HANDED
MODEL
ANTI-CRUSH DESIGN
ARTICULATED ARM
FOR SAFETY
ELECTRIC MOTOR/HYDRAULIC
JACK ASSEMBLY
REFERENCE
SEAT
PIC. 6
PIC. 4
APROLI 280 BATT is easy to install. It can be supplied either fitted with hydraulic locking device for gates up to 2 m width, or without
hydraulic locking with an electric lock for gate leaf up to 5 m.
4
Both right-hand and left-hand applications are possible just by turning over the articulated arm and fitting it to the square section shaft
of the operator. Tighten the retaining pin in its seat to fix the arm to the shaft. The assembly ie. motor/jack, fixing bracket and cover are
designed to suit both right and left-hand applications with the same method of installation. Important: the articulated arm must be fixed
so that it pushes against the gates and keeps them well pressed on to the close position gate stop.
5
HOW TO FIX APROLI 280 BATT TO A PILLAR BY EXPANDING BOLTS OR SCREWS
Before fitting the operator APROLI 280 BATT to the gate, make sure that the gate structure is adequate to be electrically operated and
that is strong enough to bear the mechanical stress of automatic operations and is well built and smooth running.
It is recommended to reinforce the gate and fix the metallic parts which may not work properly, do the necessary to prevent or correct
friction of the gate against the pavement or pillar (this must particularly apply to the gate hinges).
APPLICATION OF TWO APROLI 280 BATT ON TO A DOUBLE SWINGING GATE.
90° OPENING.
The recommended maximum gate width with APROLI 280 is 5 m. The locking type operator is recommended up to 2 m gate width. Beyond
2 m a lock is required to be fitted to the gate and the non locking type operator is advisable.
2m
VERY LARGE PILLAR
WHERE THE GATE
HINGE IS FIXED
IN THE MIDDLE
2m
LEFT-HAND
ARTICULATED
ARM
RIGHT-HAND
ARTICULATED
ARM
4 EXPANDING
BOLTS
MAINS SUPPLY
ELECTRIC CABLE
LEFT-HAND
GATE STOP IN
OPEN GATE
POSITION
90°
GATE STOP
IN CLOSE GATE
POSITION
RIGHT-HAND
GATE STOP IN
OPEN GATE
POSITION
90°
FIXING
BRACKET
NUTS WITH
WASHER
It is recommended that suitable gate stops are always fitted to
the system both in open and close gate positions. The gate stop
for open gate position is incorporated with the operator, both
right-hand and left-hand. The gate stop covers are different being
designed as handed units (part No. 2062=right-hand, 2055=left
hand). Another feature of the incorporated open gate stop is the
possibility of being adjusted to the required distance to achieve
the required opening angle, either 90° or more/less.
PIC. 5
GATE LEAF
OVERTURN
LEVEL
ARTICULATED
ARM
OPERATOR
COVER
PIC. 3
Rh
Fix the bracket to the pillar and bring the electric cable to the most suitable position so that the fixing of the articulated arm is allowed
to coincide with a solid crossing bar of the gate leaf. The shoe bracket is to be bolted or welded to the gate at a suitable distance which
is set after the first manual tests. (Release lever B page 10)
BOTH
Rh AND Lh
Lh
DISTANCE
The distance from gate pivot center to arm bolt
center is to be calculated through manual
operations of the gate before fixing the shoe
bracket. The distances on page 6-7 are merely
an application example.
RIGHT-HAND
ARTICULATED
ARM
LEFT-HAND
ARTICULATED
ARM
GRUB
SCREW
GRUB
SCREW
SQUARE
SECTION
SHAFT
COMPLETELY INSTALLED
UNIT. LEFT-HANDED
MODEL
ANTI-CRUSH DESIGN
ARTICULATED ARM
FOR SAFETY
ELECTRIC MOTOR/HYDRAULIC
JACK ASSEMBLY
REFERENCE
SEAT
PIC. 6
PIC. 4
APROLI 280 BATT is easy to install. It can be supplied either fitted with hydraulic locking device for gates up to 2 m width, or without
hydraulic locking with an electric lock for gate leaf up to 5 m.
4
Both right-hand and left-hand applications are possible just by turning over the articulated arm and fitting it to the square section shaft
of the operator. Tighten the retaining pin in its seat to fix the arm to the shaft. The assembly ie. motor/jack, fixing bracket and cover are
designed to suit both right and left-hand applications with the same method of installation. Important: the articulated arm must be fixed
so that it pushes against the gates and keeps them well pressed on to the close position gate stop.
5
20 mm FROM PILLAR
40
SURFACE LINE
EXAMPLE OF APPLICATIONS TO PILLARS OF VARIOUS DIMENSIONS. DISTANCES
ARE NOT BINDING AND ARE QUOTED FOR REFERENCE ONLY
GATE STOP
IN CLOSED
POSITION
510
GATE STOP
IN CLOSED
POSITION
CLOSED GATE LEAF
APPLICATION EXAMPLE
700x700 mm PILLAR
3 m GATE LEAF - 130 Kg
ELECTRIC
LOCK
170
APPLICATION EXAMPLE
400x400 mm PILLAR
2 m GATE LEAF - 110 Kg
20 mm FROM PILLAR
40
SURFACE LINE
20 mm FROM PILLAR
40
SURFACE LINE
CLOSED GATE LEAF
460
40
580
90
APPLICATION EXAMPLE
800x800 mm PILLAR
4 m GATE LEAF - 140 Kg
170
OPEN GATE LEAF
100°
40
OPEN GATE LEAF
100°
20 mm FROM PILLAR
SURFACE LINE
560
20 mm FROM PILLAR
40
SURFACE LINE
650
PIC. 11
PIC. 8
GATE STOP
IN CLOSED
POSITION
CLOSED GATE
LEAF
900x900
90
46
0
58
0
90
300
ELECTRIC
LOCK
GATE STOP
IN CLOSED
POSITION
ELECTRIC
LOCK
450
600x600
CLOSED GATE LEAF
GATE STOP
IN CLOSED
POSITION
ELECTRIC
LOCK
400
250
CLOSED GATE LEAF
GATE STOP
IN CLOSED
POSITION
90
APPLICATION EXAMPLE
500x500 mm PILLAR
3 m GATE LEAF - 100 Kg
620
PIC. 10
560
500x500
PIC. 7
100°
800x800
OPEN GATE LEAF
100°
OPEN GATE LEAF
40
580
460
90
90
200
350
CLOSED GATE LEAF
700X700
400x400
20 mm FROM PILLAR
40
SURFACE LINE
560
APPLICATION EXAMPLE
900x900 mm PILLAR
5 m GATE LEAF - 150 Kg
170
60
100°
OPEN GATE LEAF
APPLICATION EXAMPLE
600x600 mm PILLAR
1.8 m GATE LEAF - 140 Kg
OPEN GATE LEAF
100°
PIC. 12
PIC. 9
6
It is recommended that all gates are provided with adequate gate stops both in open and closed gate positions. When a 5 m gate is
involved the weight must not be greater than 200 Kg and it is required to fit the gate with an electric lock, the operator must be non
locking type. With gates up to 2 m width, it is possible to install the locking type without electric lock.
See the examples and drawings on pages 6 - 7.
7
20 mm FROM PILLAR
40
SURFACE LINE
EXAMPLE OF APPLICATIONS TO PILLARS OF VARIOUS DIMENSIONS. DISTANCES
ARE NOT BINDING AND ARE QUOTED FOR REFERENCE ONLY
GATE STOP
IN CLOSED
POSITION
510
GATE STOP
IN CLOSED
POSITION
CLOSED GATE LEAF
APPLICATION EXAMPLE
700x700 mm PILLAR
3 m GATE LEAF - 130 Kg
ELECTRIC
LOCK
170
APPLICATION EXAMPLE
400x400 mm PILLAR
2 m GATE LEAF - 110 Kg
20 mm FROM PILLAR
40
SURFACE LINE
20 mm FROM PILLAR
40
SURFACE LINE
CLOSED GATE LEAF
460
40
580
90
APPLICATION EXAMPLE
800x800 mm PILLAR
4 m GATE LEAF - 140 Kg
170
OPEN GATE LEAF
100°
40
OPEN GATE LEAF
100°
20 mm FROM PILLAR
SURFACE LINE
560
20 mm FROM PILLAR
40
SURFACE LINE
650
PIC. 11
PIC. 8
GATE STOP
IN CLOSED
POSITION
CLOSED GATE
LEAF
900x900
90
46
0
58
0
90
300
ELECTRIC
LOCK
GATE STOP
IN CLOSED
POSITION
ELECTRIC
LOCK
450
600x600
CLOSED GATE LEAF
GATE STOP
IN CLOSED
POSITION
ELECTRIC
LOCK
400
250
CLOSED GATE LEAF
GATE STOP
IN CLOSED
POSITION
90
APPLICATION EXAMPLE
500x500 mm PILLAR
3 m GATE LEAF - 100 Kg
620
PIC. 10
560
500x500
PIC. 7
100°
800x800
OPEN GATE LEAF
100°
OPEN GATE LEAF
40
580
460
90
90
200
350
CLOSED GATE LEAF
700X700
400x400
20 mm FROM PILLAR
40
SURFACE LINE
560
APPLICATION EXAMPLE
900x900 mm PILLAR
5 m GATE LEAF - 150 Kg
170
60
100°
OPEN GATE LEAF
APPLICATION EXAMPLE
600x600 mm PILLAR
1.8 m GATE LEAF - 140 Kg
OPEN GATE LEAF
100°
PIC. 12
PIC. 9
6
It is recommended that all gates are provided with adequate gate stops both in open and closed gate positions. When a 5 m gate is
involved the weight must not be greater than 200 Kg and it is required to fit the gate with an electric lock, the operator must be non
locking type. With gates up to 2 m width, it is possible to install the locking type without electric lock.
See the examples and drawings on pages 6 - 7.
7
ON TO “0” THE DELAY
IS OUT OF SERVICE
st
1 CHANNEL
24 V OUTPUT
70
LEAF DELAY
TIMER CLOSE
+DWELL TIME
3
4
1
2
3
4
5
RUN
+ MOTOR
OPEN & CLOSE TIME
4
CAPACITORS
12,5µF
6
5
6
8
9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25
COMMON
ELECTRIC MOTORS
SINGLE-PHASE
230 V SINGLE-PHASE
SUPPLY VOLTAGE
LED No. 1 - It switches on when voltage is supplied
SAFETY CONTACT N.C.
ALL OPERATIONS
OPEN, CLOSE AND
REVERSE
RADIO CONTACT
Max permitted load:
2 pairs photocells
1 radio receiver
8
24 V
OUTPUT A.C.
PULSE TWICE CONSECUTIVELY
TO OPEN BOTH GATE LEAFS
24 V INDICATOR - 3 W max.
VOLTAGE OUTPUT
ELECTRIC LOCK SUPPLY
COMMON
RADIO CONTACT N.O.
STOP SWITCH N.C. CONTACT
CLOSE SWITCH N.O. CONTACT
OPEN SWITCH N.O. CONTACT
COMMON
N.C. CONTACT
PHOTOCELLS
7
M2
230 V FLASHING LAMP
25 W max.
= PHOTOCELLS 2nd PAIR =
Inside photocells N.C. contact
If obstracted, they prevent the gates from opening
reverse gate direction during close cycle
Should more pairs of photocells be required
than the recommended quantity, fit an auxiliary
transformer outside the control box.
M1
PEDESTRIAN MODE
ONE PULSE OPENS
ONE GATE LEAF ONLY
5
10
7
OFF
4
3
COMMON
1 2 3 4 5 6 7 8
2
230 Volt
MAINS SWITCH
1 AMP. FUSE
24 V OUTPUT
TERMINALS 12-13
12,5µF
1
2
FLASHING LAMP
630 mA FUSE
FUSE 5 AMPS
9
ON
3
+
—
8
DIP-SWITCH
B
FUSE
630 mA
MICROPROCESSOR
TERMINAL FOR
CONNECTIONS TO
PUSH BUTTONS PULIN 3
ON
1
TIMER SWITCHES
RADIO CONTROL
PLUG-IN CARD SUPPORT
26
27
28
The below diagram is general for an application of the operator and the complementary accessories which are supplied with the unit.
13 exp
CONNECTION DIAGRAM FOR SWING GATES
11
15
12
16
13
6
NOTE WELL: For special applications, ie. to switch
on lights - CCTV etc., SOLID STATE RELAYS are
recommended to be used only. Standard relays
would affect the micro-processor.
NOTE WELL: THIS PANEL IS TESTED TO OPERATE GATES ONLY
THROUGH FADINI ACCESSORIES. NO GUARANTEE FOR
ACCESSORIES OF OTHER MAKE OR SPECIAL APPLICATIONS.
Drwg. No.
14
7
6
8
17
1643 P.C. BOARD
9
ALL THE ELECTRICAL EQUIPMENT MUST BE EARTH CONNECTED
ELECTRICAL WIRING DIAGRAM OF THE ELECTRONIC
PROGRAMMER
PIC. 13
OPEN
CLOSE
The 6 LEDs on the P.C. board indicate the following:
Led No. 1 It switches on when voltage is supplied
Led No. 2 Photocells - Normally on. It switches off when the
photocells are obstructed
Led No. 3 Open - It switches on when the respective switch is
activated
Led No. 4 Close - It switches on when the respective switch it
activated
Led No. 5 Stop - Normally on. it switches off when the respective
switch is activated
Led No. 6 Radio - It switches on whenever a pulse is given, either
from remote control, keyswitch or push buttons.
TERMINAL BOARD
STOP
STOP N.C. CONTAC
CLOSE N.O. CONTACT
OPEN N.O. CONTACT
COMMON
E. CONNECTIONS
KEYSWITCH SECH 15
To perform the electrical work, connections are as per diagrams on pages 8-9. Once the connections have been made, adjust the
switches in the control box so that the sequence of operations occurs as pre-set. Set DIP switch 3 on automatic and check if the working
times meet your requirements. On semiautomatic mode, one pulse opens the gates, a second pulse is needed to close the gates.
Sx 2°
Dx 1°
PLEASE NOTE: Should the electric motors
fail to start properly because of power
shortage, connect some extra 12.5 µF
capacitors to the phase and common
terminals as shown in pic. 16.
Terminal board
Elpro 13 exp
16 17 18 19 20 21 22 23
Drwg. No. 1643
12.5 µF
PIC. 14
8
PHASE M2
CONNECTION TO THE “PULIN 3” PUSH
BUTTONS WITH STATUS INDICATION LEDS.
PHASE M2
CLOSE
9 - RADIO TRANSMITTER TYPE A43/ 2TR
10 - KEYSWITCH TYPE SECH 15
11 - ELECTRIC LOCK
12 - PHOTOCELL TRANSMITTER DIFO 33. OUTSIDE
13 - RIGHT-HAND OPERATOR TYPE APROLI 280 BATT
14 - PHOTOCELL RECEIVER TYPE DIFO 33 OUTSIDE
15 - LEFT-HAND OPERATOR TYPE APROLI 280 BATT
16 - MECHANICAL LATCH
17 - POST WITH PHOTOCELL PROJECTOR TYPE DIFO 33
COMMON M2
STOP
N.O.
1 - STEMMED AERIAL A 43
2 - LAPI 2 FLASHING LAMP
3 - 230 V - 50/60 Hz MAINS SWITCH WITH
MAGNETIC-THERMAL DIFFERENTIAL TYPE 0.03 A
(beyond 100 m distance 2.5 mm Ø cables are recommended)
4 - RADIO RECEIVER CARD A 43/2R
5 - ELECTRONIC PROGRAMMER TYPE ELPRO 13 exp
6 - JUNCTION BOX
7 - WALL PUSH BUTTONS PULIN 3 (INSIDE HOME)
8 - POST WITH PHOTOCELL RECEIVER TYPE DIFO 33
PHASE M1
OPEN
N.C.
Once the connections have been made, do the first switching
test through the control panel. Set the motor run timer so that
the motor is allowed to run 4 - 5 seconds more than the gates.
Set the other timers to meet the site requirements. Set DIP switch
B No. 3 to automatic (ON): on pulsing to 4 - 8 the gates must be
operated as pre-set, ie. opening and only after the dwell time,
closing. Adjust the times through the respective timers. (See No.
07, 08 and 09 drwg. No. 1643).
With DIP switch "B" No. 3 to semiautomatic (OFF) one pulse opens
the gates, a second pulse to 5 - 8 is needed to close the gates.
Any one pulse to 7 - 8 will open, close or reverse the gates
independently from the operation being performed. It is
recommended to carefully read the instructions in the control
box to have all the functions performed correctly.
PHASE M1
N.O.
26 27 28 3
6
COMMON M1
5
COMMON
4
COMMON
3
PIC. 15
PIC. 16
9
12.5 µF
ON TO “0” THE DELAY
IS OUT OF SERVICE
st
1 CHANNEL
24 V OUTPUT
70
LEAF DELAY
TIMER CLOSE
+DWELL TIME
3
4
1
2
3
4
5
RUN
+ MOTOR
OPEN & CLOSE TIME
4
CAPACITORS
12,5µF
6
5
6
8
9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25
COMMON
ELECTRIC MOTORS
SINGLE-PHASE
230 V SINGLE-PHASE
SUPPLY VOLTAGE
LED No. 1 - It switches on when voltage is supplied
SAFETY CONTACT N.C.
ALL OPERATIONS
OPEN, CLOSE AND
REVERSE
RADIO CONTACT
Max permitted load:
2 pairs photocells
1 radio receiver
8
24 V
OUTPUT A.C.
PULSE TWICE CONSECUTIVELY
TO OPEN BOTH GATE LEAFS
24 V INDICATOR - 3 W max.
VOLTAGE OUTPUT
ELECTRIC LOCK SUPPLY
COMMON
RADIO CONTACT N.O.
STOP SWITCH N.C. CONTACT
CLOSE SWITCH N.O. CONTACT
OPEN SWITCH N.O. CONTACT
COMMON
N.C. CONTACT
PHOTOCELLS
7
M2
230 V FLASHING LAMP
25 W max.
= PHOTOCELLS 2nd PAIR =
Inside photocells N.C. contact
If obstracted, they prevent the gates from opening
reverse gate direction during close cycle
Should more pairs of photocells be required
than the recommended quantity, fit an auxiliary
transformer outside the control box.
M1
PEDESTRIAN MODE
ONE PULSE OPENS
ONE GATE LEAF ONLY
5
10
7
OFF
4
3
COMMON
1 2 3 4 5 6 7 8
2
230 Volt
MAINS SWITCH
1 AMP. FUSE
24 V OUTPUT
TERMINALS 12-13
12,5µF
1
2
FLASHING LAMP
630 mA FUSE
FUSE 5 AMPS
9
ON
3
+
—
8
DIP-SWITCH
B
FUSE
630 mA
MICROPROCESSOR
TERMINAL FOR
CONNECTIONS TO
PUSH BUTTONS PULIN 3
ON
1
TIMER SWITCHES
RADIO CONTROL
PLUG-IN CARD SUPPORT
26
27
28
The below diagram is general for an application of the operator and the complementary accessories which are supplied with the unit.
13 exp
CONNECTION DIAGRAM FOR SWING GATES
11
15
12
16
13
6
NOTE WELL: For special applications, ie. to switch
on lights - CCTV etc., SOLID STATE RELAYS are
recommended to be used only. Standard relays
would affect the micro-processor.
NOTE WELL: THIS PANEL IS TESTED TO OPERATE GATES ONLY
THROUGH FADINI ACCESSORIES. NO GUARANTEE FOR
ACCESSORIES OF OTHER MAKE OR SPECIAL APPLICATIONS.
Drwg. No.
14
7
6
8
17
1643 P.C. BOARD
9
ALL THE ELECTRICAL EQUIPMENT MUST BE EARTH CONNECTED
ELECTRICAL WIRING DIAGRAM OF THE ELECTRONIC
PROGRAMMER
PIC. 13
OPEN
CLOSE
The 6 LEDs on the P.C. board indicate the following:
Led No. 1 It switches on when voltage is supplied
Led No. 2 Photocells - Normally on. It switches off when the
photocells are obstructed
Led No. 3 Open - It switches on when the respective switch is
activated
Led No. 4 Close - It switches on when the respective switch it
activated
Led No. 5 Stop - Normally on. it switches off when the respective
switch is activated
Led No. 6 Radio - It switches on whenever a pulse is given, either
from remote control, keyswitch or push buttons.
TERMINAL BOARD
STOP
STOP N.C. CONTAC
CLOSE N.O. CONTACT
OPEN N.O. CONTACT
COMMON
E. CONNECTIONS
KEYSWITCH SECH 15
To perform the electrical work, connections are as per diagrams on pages 8-9. Once the connections have been made, adjust the
switches in the control box so that the sequence of operations occurs as pre-set. Set DIP switch 3 on automatic and check if the working
times meet your requirements. On semiautomatic mode, one pulse opens the gates, a second pulse is needed to close the gates.
Sx 2°
Dx 1°
PLEASE NOTE: Should the electric motors
fail to start properly because of power
shortage, connect some extra 12.5 µF
capacitors to the phase and common
terminals as shown in pic. 16.
Terminal board
Elpro 13 exp
16 17 18 19 20 21 22 23
Drwg. No. 1643
12.5 µF
PIC. 14
8
PHASE M2
CONNECTION TO THE “PULIN 3” PUSH
BUTTONS WITH STATUS INDICATION LEDS.
PHASE M2
CLOSE
9 - RADIO TRANSMITTER TYPE A43/ 2TR
10 - KEYSWITCH TYPE SECH 15
11 - ELECTRIC LOCK
12 - PHOTOCELL TRANSMITTER DIFO 33. OUTSIDE
13 - RIGHT-HAND OPERATOR TYPE APROLI 280 BATT
14 - PHOTOCELL RECEIVER TYPE DIFO 33 OUTSIDE
15 - LEFT-HAND OPERATOR TYPE APROLI 280 BATT
16 - MECHANICAL LATCH
17 - POST WITH PHOTOCELL PROJECTOR TYPE DIFO 33
COMMON M2
STOP
N.O.
1 - STEMMED AERIAL A 43
2 - LAPI 2 FLASHING LAMP
3 - 230 V - 50/60 Hz MAINS SWITCH WITH
MAGNETIC-THERMAL DIFFERENTIAL TYPE 0.03 A
(beyond 100 m distance 2.5 mm Ø cables are recommended)
4 - RADIO RECEIVER CARD A 43/2R
5 - ELECTRONIC PROGRAMMER TYPE ELPRO 13 exp
6 - JUNCTION BOX
7 - WALL PUSH BUTTONS PULIN 3 (INSIDE HOME)
8 - POST WITH PHOTOCELL RECEIVER TYPE DIFO 33
PHASE M1
OPEN
N.C.
Once the connections have been made, do the first switching
test through the control panel. Set the motor run timer so that
the motor is allowed to run 4 - 5 seconds more than the gates.
Set the other timers to meet the site requirements. Set DIP switch
B No. 3 to automatic (ON): on pulsing to 4 - 8 the gates must be
operated as pre-set, ie. opening and only after the dwell time,
closing. Adjust the times through the respective timers. (See No.
07, 08 and 09 drwg. No. 1643).
With DIP switch "B" No. 3 to semiautomatic (OFF) one pulse opens
the gates, a second pulse to 5 - 8 is needed to close the gates.
Any one pulse to 7 - 8 will open, close or reverse the gates
independently from the operation being performed. It is
recommended to carefully read the instructions in the control
box to have all the functions performed correctly.
PHASE M1
N.O.
26 27 28 3
6
COMMON M1
5
COMMON
4
COMMON
3
PIC. 15
PIC. 16
9
12.5 µF
The two safety pressure valves are identified by colours: “A” open is red; “C” close is green. They are located in the front of the
motor/pump unit, easy to reach for setting operations in order to meet the power requirements Pic. 17.
Once the valves are set, you can fit the cover and the other accessories.
RELEASE BY 1 TURN
TO LET THE AIR OUT
OF OIL RESERVOIR
APROLI 280 BATT SPECIAL VERSION CODE 287
The flow regulator has the purpose of mantaining
constant the rotation speed of the shaft that operates
the articulated arm.
SPEED
FLOW
REGULATOR
OPEN
SPEED
SPEED
“S”
PIC. 18
“S”
LESS
POWER
OIL FADINI A 15 BY AGIP
®
404
TECHNICAL SPECIFICATIONS
FIXING
BRACKET
BATT
OIL-HYDRAULIC
s.n.c.
Via Mantova, 177/A - 37053 Cerea (VR) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054
“C”
402
260
THIS STICKER IS FITTED ON THE OIL RESERVOIR
“A”
W
250
HP
0.25
VOLTS
230
A
1.2
r.p.m.
1˙350
Hz
50
Nm
196.2
µF
12.5
100
ELECTRIC MOTOR/
JACK ASSEMBLY
Degree of protection IP 555
345
290
MOTOR 2 PHASE
106
190
MAXIMUM
PRESSURE VALVE
“OPEN”
RED IN COLOUR
SPEED
RELEASE
IMPORTANT
AFTER INSTALLING BY 1 TURN
APROLI 280 BATT
AIR BLEED
MAXIMUM
PRESSURE VALVE
“CLOSE”
GREEN IN COLOUR
CONSTANT
SPEED
FLOW
REGULATOR
CLOSE
MORE
POWER
Working pressure max. 3 MPa (30 Bars)
EARTH
190
OIL FADINI A15 BY AGIP
MADE IN ITALY
240
20x20
407
139
35
“B” RELEASE LEVER
50
PROTECTION
COVER
520
PULL THE LEVER DOWNWARDS TO RELEASE
218
570
580
460
PIC. 17
The setting of the safety pressure valves is to be done so to achieve the exact amount of power required to safely operate the gate.
The more you turn the screw clockwise, the more you increase the power of the operator.
Please note, once APROLI 280 has been fixed, unscrew the air bleed screw by one turn. This screw is fitted on the cap of the oil
reservoire, where the mains cable is led to the motor.
Should the operator “APROLI 280” be removed for maintenance or repairing, tighten the screw "S" to prevent oil from coming out during
handling.
In case of power failure, to open the two leafs fitted with APROLI 280 BATT non-loking type, you have to release the electric lock with
the key and push the gate leafs open by hand in a very smooth way. Should the operator be fitted with locking device, first pull the
release lever "B" downwards and then push open (Pic. 17). Open the hinged door to have access to the lever.
NEVER CUT THE ELECTRIC CABLES
- Please note that the electric cables must be removed from their terminals by loosening the fastening screws. Never cut the electric
cables. Also make sure that the 230V mains switch No. 3 is off before removing the cables. See page 9, pic. 15.
- Only by keeping to these fitting instructions it can be achieved a reliable installation and the best performance of the operator.
The installation is fully under the responsability of the installation agent, even if it consists entirelly of Fadini products as listed in this
booklet. It is advisable that the system is installed in full compliance with these instructions and in observance of the existing laws
which rule automatic doors.
- All the information, specifications and drawings contained herein are subject to any change that is considered appropriate by the
manufacturer with any previous notice.
10
LEFT-HAND ARTICULATED ARM
WITH RETAINING SCREW AND SHOE
580
520
Lh
460
570
TURN IT OVER TO
MAKE IT RIGHT-HAND
RIGHT-HAND ARTICULATED ARM
WITH RETAINING SCREW AND SHOE
Rh
PIC. 19
HYDRAULIC PUMP
ELECTRIC MOTOR
Pump flow rate - P3 ...........................................................0.85 l/min.
Working pressure ....................................................1 MPa (10 bars)
Max. pressure...........................................................3 MPa (30 bars)
Working temperature ....................................................–20°C +80°C
Opening time..................................................................................23 s
Oil type ..............................................................A 15 FADINI by AGIP
Max. shaft rotation angle............................................................205°
Rated torque .........................................................................196.2 Nm
Static weight of operator ..........................................................11 Kg
IP Standards...............................................................................IP 555
Power output .........................................................0.18 KW (0.25 HP)
Supply voltage / Frequency .........................................230 V - 50 Hz
Absorbed current ........................................................................1.2 A
Absorbed power........................................................................250 W
Capacitor...................................................................................12.5 µF
Motor rotation speed.......................................................1˙350 r.p.m.
Intermittent service........................................................................S 3
Duty cycle ................23 sec. Open - 30 sec. Dwell - 23 sec. Close
Time of one complete cycle ........................................................76 s
No. of complete cycles Open - Dwell - Close ....................47/hour
No. cycles a year, 8 hours a day ..........................................137˙000
11
The two safety pressure valves are identified by colours: “A” open is red; “C” close is green. They are located in the front of the
motor/pump unit, easy to reach for setting operations in order to meet the power requirements Pic. 17.
Once the valves are set, you can fit the cover and the other accessories.
RELEASE BY 1 TURN
TO LET THE AIR OUT
OF OIL RESERVOIR
APROLI 280 BATT SPECIAL VERSION CODE 287
The flow regulator has the purpose of mantaining
constant the rotation speed of the shaft that operates
the articulated arm.
SPEED
FLOW
REGULATOR
OPEN
SPEED
SPEED
“S”
PIC. 18
“S”
LESS
POWER
OIL FADINI A 15 BY AGIP
®
404
TECHNICAL SPECIFICATIONS
FIXING
BRACKET
BATT
OIL-HYDRAULIC
s.n.c.
Via Mantova, 177/A - 37053 Cerea (VR) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054
“C”
402
260
THIS STICKER IS FITTED ON THE OIL RESERVOIR
“A”
W
250
HP
0.25
VOLTS
230
A
1.2
r.p.m.
1˙350
Hz
50
Nm
196.2
µF
12.5
100
ELECTRIC MOTOR/
JACK ASSEMBLY
Degree of protection IP 555
345
290
MOTOR 2 PHASE
106
190
MAXIMUM
PRESSURE VALVE
“OPEN”
RED IN COLOUR
SPEED
RELEASE
IMPORTANT
AFTER INSTALLING BY 1 TURN
APROLI 280 BATT
AIR BLEED
MAXIMUM
PRESSURE VALVE
“CLOSE”
GREEN IN COLOUR
CONSTANT
SPEED
FLOW
REGULATOR
CLOSE
MORE
POWER
Working pressure max. 3 MPa (30 Bars)
EARTH
190
OIL FADINI A15 BY AGIP
MADE IN ITALY
240
20x20
407
139
35
“B” RELEASE LEVER
50
PROTECTION
COVER
520
PULL THE LEVER DOWNWARDS TO RELEASE
218
570
580
460
PIC. 17
The setting of the safety pressure valves is to be done so to achieve the exact amount of power required to safely operate the gate.
The more you turn the screw clockwise, the more you increase the power of the operator.
Please note, once APROLI 280 has been fixed, unscrew the air bleed screw by one turn. This screw is fitted on the cap of the oil
reservoire, where the mains cable is led to the motor.
Should the operator “APROLI 280” be removed for maintenance or repairing, tighten the screw "S" to prevent oil from coming out during
handling.
In case of power failure, to open the two leafs fitted with APROLI 280 BATT non-loking type, you have to release the electric lock with
the key and push the gate leafs open by hand in a very smooth way. Should the operator be fitted with locking device, first pull the
release lever "B" downwards and then push open (Pic. 17). Open the hinged door to have access to the lever.
NEVER CUT THE ELECTRIC CABLES
- Please note that the electric cables must be removed from their terminals by loosening the fastening screws. Never cut the electric
cables. Also make sure that the 230V mains switch No. 3 is off before removing the cables. See page 9, pic. 15.
- Only by keeping to these fitting instructions it can be achieved a reliable installation and the best performance of the operator.
The installation is fully under the responsability of the installation agent, even if it consists entirelly of Fadini products as listed in this
booklet. It is advisable that the system is installed in full compliance with these instructions and in observance of the existing laws
which rule automatic doors.
- All the information, specifications and drawings contained herein are subject to any change that is considered appropriate by the
manufacturer with any previous notice.
10
LEFT-HAND ARTICULATED ARM
WITH RETAINING SCREW AND SHOE
580
520
Lh
460
570
TURN IT OVER TO
MAKE IT RIGHT-HAND
RIGHT-HAND ARTICULATED ARM
WITH RETAINING SCREW AND SHOE
Rh
PIC. 19
HYDRAULIC PUMP
ELECTRIC MOTOR
Pump flow rate - P3 ...........................................................0.85 l/min.
Working pressure ....................................................1 MPa (10 bars)
Max. pressure...........................................................3 MPa (30 bars)
Working temperature ....................................................–20°C +80°C
Opening time..................................................................................23 s
Oil type ..............................................................A 15 FADINI by AGIP
Max. shaft rotation angle............................................................205°
Rated torque .........................................................................196.2 Nm
Static weight of operator ..........................................................11 Kg
IP Standards...............................................................................IP 555
Power output .........................................................0.18 KW (0.25 HP)
Supply voltage / Frequency .........................................230 V - 50 Hz
Absorbed current ........................................................................1.2 A
Absorbed power........................................................................250 W
Capacitor...................................................................................12.5 µF
Motor rotation speed.......................................................1˙350 r.p.m.
Intermittent service........................................................................S 3
Duty cycle ................23 sec. Open - 30 sec. Dwell - 23 sec. Close
Time of one complete cycle ........................................................76 s
No. of complete cycles Open - Dwell - Close ....................47/hour
No. cycles a year, 8 hours a day ..........................................137˙000
11
Lineagrafica
280 BATT
WARNINGS
- It is recommended to keep to the instructions here outlined - check the specifications on the motor sticker with your mains
supply.
- Dispose properly of the packaging: cardboard, nylon, polystyrene, through specializing companies.
- Should the operator be removed, do not cut the electric cable. This must be properly removed from the terminal board in the
junction box.
- Switch off the mains switch before removing the junction box cover where the electric cable of APROLI 280 BATT is terminated.
- All the system must be earthed by using the yellow/green wire, marked by its specific symbol.
- It is recommended to read the regulations, suggestions and remarks quoted in the booklet "Warnings".
- Should APROLI 280 BATT be removed for maintenance, servicing or repair, tighten the air bleeding screw to prevent oil coming
out of the reservoir during transport.
Meccanica Fadini recommends the control panel ELPRO 13 CEI to
achieve an installation that is in conformity to the existing safety
standards.
The electronic programmer ELPRO 13 incorporates and can provide
all the functions which are required by the most demanding
applications with swinging gates.
In addition to the standard features of a conventional control box
type ELPRO 9 (see page 8 pic. 13) the following requirements can
be provided: “stroke reversing pulse”, pedestrian mode, stop in any
gate position by holding down the remote control button. Among
the added features and improvements of ELPRO 13 in conformity to
the European safety standards, there is the mains rotary switch: it
is fitted to the box cover and switches off the mains voltage whenever
the cover is removed.
3-2003
APROLI
STATIC GATE WEIGHT
400 Kg each leaf
13 CEI
SINGLE-PHASE
l apricancel lo
CUT OFF MAINS SWITCH
The “CE” mark certifies that the operator conforms to the essential
requirements of the European Directive art. 10 EEC 73/23, in relation
to the manufacturer’s declaration for the supplied items, in
compliance with the body of the regulations ISO 9000= UNI EN 29000.
Automation in conformity to EN 12453, EN 12445 safety standard.
The growth of MECCANICA FADINI has always been based
on the development of guaranteed products thanks to our
“TOTAL QUALITY CONTROL” system which ensures constant
quality standards, updated knowledge of the European
Standards and compliance with their requirements, in view
of an ever increasing process of improvement.
EUROPEAN MARK CERTIFYING CONFORMITY
TO THE ESSENTIAL REQUIREMENTS OF THE
STANDARDS 98/37 EC
• DECLARATION OF CONFORMITY
• GENERAL WARNINGS
• EN 12453, EN 12445 STANDARDS
• CEI EN 60204-1 STANDARDS
• WARRANTY CERTIFICATE ON THE CUSTOMER’S REQUEST
®
Made in Italy
GB
®
s.n.c.
AUTOMATIC GATE MANUFACTURERS
Distributor’s box
The manufacturers reserve the right to change the products without any previous notice
Via Mantova, 177/A - 37053 Cerea (Verona) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054 - e-mail: info@fadini.net - www.fadini.net
INSTALLATION MANUAL
®