Download INSTALLATION MANUAL - fintotoegangsbeheer.nl
Transcript
Lineagrafica 280 BATT WARNINGS - It is recommended to keep to the instructions here outlined - check the specifications on the motor sticker with your mains supply. - Dispose properly of the packaging: cardboard, nylon, polystyrene, through specializing companies. - Should the operator be removed, do not cut the electric cable. This must be properly removed from the terminal board in the junction box. - Switch off the mains switch before removing the junction box cover where the electric cable of APROLI 280 BATT is terminated. - All the system must be earthed by using the yellow/green wire, marked by its specific symbol. - It is recommended to read the regulations, suggestions and remarks quoted in the booklet "Warnings". - Should APROLI 280 BATT be removed for maintenance, servicing or repair, tighten the air bleeding screw to prevent oil coming out of the reservoir during transport. Meccanica Fadini recommends the control panel ELPRO 13 CEI to achieve an installation that is in conformity to the existing safety standards. The electronic programmer ELPRO 13 incorporates and can provide all the functions which are required by the most demanding applications with swinging gates. In addition to the standard features of a conventional control box type ELPRO 9 (see page 8 pic. 13) the following requirements can be provided: “stroke reversing pulse”, pedestrian mode, stop in any gate position by holding down the remote control button. Among the added features and improvements of ELPRO 13 in conformity to the European safety standards, there is the mains rotary switch: it is fitted to the box cover and switches off the mains voltage whenever the cover is removed. 3-2003 APROLI STATIC GATE WEIGHT 400 Kg each leaf 13 CEI SINGLE-PHASE l apricancel lo CUT OFF MAINS SWITCH The “CE” mark certifies that the operator conforms to the essential requirements of the European Directive art. 10 EEC 73/23, in relation to the manufacturer’s declaration for the supplied items, in compliance with the body of the regulations ISO 9000= UNI EN 29000. Automation in conformity to EN 12453, EN 12445 safety standard. The growth of MECCANICA FADINI has always been based on the development of guaranteed products thanks to our “TOTAL QUALITY CONTROL” system which ensures constant quality standards, updated knowledge of the European Standards and compliance with their requirements, in view of an ever increasing process of improvement. EUROPEAN MARK CERTIFYING CONFORMITY TO THE ESSENTIAL REQUIREMENTS OF THE STANDARDS 98/37 EC • DECLARATION OF CONFORMITY • GENERAL WARNINGS • EN 12453, EN 12445 STANDARDS • CEI EN 60204-1 STANDARDS • WARRANTY CERTIFICATE ON THE CUSTOMER’S REQUEST ® Made in Italy GB ® s.n.c. AUTOMATIC GATE MANUFACTURERS Distributor’s box The manufacturers reserve the right to change the products without any previous notice Via Mantova, 177/A - 37053 Cerea (Verona) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054 - e-mail: info@fadini.net - www.fadini.net INSTALLATION MANUAL ® APROLI 280 BATT CUTAWAY VIEW OF THE ELECTRIC MOTOR ASSEMBLY AND HYDRAULIC JACK AVAILABLE TYPES: NON LOCKING - LOCKING - WITH FLOW REGULATOR INSTRUCTIONS FOR THE INSTALLATION OF APROLI 280 BATT TO SWINGING DOUBLE GATES WITH VERY LARGE PILLARS it is recommended to follow these instructions to achieve a perfect application of the operator. BASE AND FIXING BRACKET STUD BOLT ASSEMBLY ELEC. MOTOR HYDR. JACK PROTECTION COVER FIXING SCREWS TWO-WAY LOCKING VALVE ASSEMBLY PRESSURE SAFETY VALVE “CLOSE” GREEN PRESSURE SAFETY VALVE “OPEN” RED OIL RESERVOIR TERMINAL PLUG COVER “C” “A” TERMINAL PLUG EARTH WIRE OIL RESERVOIR REAR CAP 0.25 HP ELECTRIC MOTOR HYDRAULIC LOBE PUMP JACK END CAP 1st PISTON Lh RACK “B” RELEASE LEVER PISTON LINER OPEN STOP ASSEMBLY 14 E22 NUT, STUD BOLT, ADJUSTER COVER. LEFT-HAND WASHER Ø 8.5 8M E13 NUT RETAINING DRIVING BENDED ARM GRUB SCREW BENDED PLUG PROFILE ARM BOLT AND NUT STRAIGHT ARM COVER BUSH STRAIGHT ARM. ADJUSTABLE FIXING SHOE ARTICULATED ARM LEFT-HANDED SHAFT SUPPORT SQUARE INDENTED SHAFT SCREW FOR ADJUSTMENT PIC. 2 2nd PISTON PISTON LINER MAIN ASSEMBLY BLOCK WITH MOTOR AND HYDR. JACK First loosen the fastening screws to remove the cover. To do this, open the hinged door with the supplied key; one of the two fastening screws is there. After the removal of the cover, the electro-hydraulic assembly is fully exposed, ie. “electric motor/hydraulic jack” fitted with the pressure safety valves that control the thrust/pushing power of the operator and the emergency release in events like power failure. It also includes a bracket, designed to provide fixing facility to a wall or pillar and a suitable outlet for the cables; an articulated arm, adjustable to meet the most various distance requirements on site applications; and a shoe bracket to be fixed to the gate. The operator is supplied already pre-filled with special oil to suit both high and low environment temperatures. It allows the correct performance of APROLI 280 BATT within a temperature range from –20°C to +80°C. APROLI 280 BATT is produced and tested in the workshops of MECCANICA FADINI which guarantees the long lasting reliability of this product in time. PIC. 1 2 3 APROLI 280 BATT CUTAWAY VIEW OF THE ELECTRIC MOTOR ASSEMBLY AND HYDRAULIC JACK AVAILABLE TYPES: NON LOCKING - LOCKING - WITH FLOW REGULATOR INSTRUCTIONS FOR THE INSTALLATION OF APROLI 280 BATT TO SWINGING DOUBLE GATES WITH VERY LARGE PILLARS it is recommended to follow these instructions to achieve a perfect application of the operator. BASE AND FIXING BRACKET STUD BOLT ASSEMBLY ELEC. MOTOR HYDR. JACK PROTECTION COVER FIXING SCREWS TWO-WAY LOCKING VALVE ASSEMBLY PRESSURE SAFETY VALVE “CLOSE” GREEN PRESSURE SAFETY VALVE “OPEN” RED OIL RESERVOIR TERMINAL PLUG COVER “C” “A” TERMINAL PLUG EARTH WIRE OIL RESERVOIR REAR CAP 0.25 HP ELECTRIC MOTOR HYDRAULIC LOBE PUMP JACK END CAP 1st PISTON Lh RACK “B” RELEASE LEVER PISTON LINER OPEN STOP ASSEMBLY 14 E22 NUT, STUD BOLT, ADJUSTER COVER. LEFT-HAND WASHER Ø 8.5 8M E13 NUT RETAINING DRIVING BENDED ARM GRUB SCREW BENDED PLUG PROFILE ARM BOLT AND NUT STRAIGHT ARM COVER BUSH STRAIGHT ARM. ADJUSTABLE FIXING SHOE ARTICULATED ARM LEFT-HANDED SHAFT SUPPORT SQUARE INDENTED SHAFT SCREW FOR ADJUSTMENT PIC. 2 2nd PISTON PISTON LINER MAIN ASSEMBLY BLOCK WITH MOTOR AND HYDR. JACK First loosen the fastening screws to remove the cover. To do this, open the hinged door with the supplied key; one of the two fastening screws is there. After the removal of the cover, the electro-hydraulic assembly is fully exposed, ie. “electric motor/hydraulic jack” fitted with the pressure safety valves that control the thrust/pushing power of the operator and the emergency release in events like power failure. It also includes a bracket, designed to provide fixing facility to a wall or pillar and a suitable outlet for the cables; an articulated arm, adjustable to meet the most various distance requirements on site applications; and a shoe bracket to be fixed to the gate. The operator is supplied already pre-filled with special oil to suit both high and low environment temperatures. It allows the correct performance of APROLI 280 BATT within a temperature range from –20°C to +80°C. APROLI 280 BATT is produced and tested in the workshops of MECCANICA FADINI which guarantees the long lasting reliability of this product in time. PIC. 1 2 3 HOW TO FIX APROLI 280 BATT TO A PILLAR BY EXPANDING BOLTS OR SCREWS Before fitting the operator APROLI 280 BATT to the gate, make sure that the gate structure is adequate to be electrically operated and that is strong enough to bear the mechanical stress of automatic operations and is well built and smooth running. It is recommended to reinforce the gate and fix the metallic parts which may not work properly, do the necessary to prevent or correct friction of the gate against the pavement or pillar (this must particularly apply to the gate hinges). APPLICATION OF TWO APROLI 280 BATT ON TO A DOUBLE SWINGING GATE. 90° OPENING. The recommended maximum gate width with APROLI 280 is 5 m. The locking type operator is recommended up to 2 m gate width. Beyond 2 m a lock is required to be fitted to the gate and the non locking type operator is advisable. 2m VERY LARGE PILLAR WHERE THE GATE HINGE IS FIXED IN THE MIDDLE 2m LEFT-HAND ARTICULATED ARM RIGHT-HAND ARTICULATED ARM 4 EXPANDING BOLTS MAINS SUPPLY ELECTRIC CABLE LEFT-HAND GATE STOP IN OPEN GATE POSITION 90° GATE STOP IN CLOSE GATE POSITION RIGHT-HAND GATE STOP IN OPEN GATE POSITION 90° FIXING BRACKET NUTS WITH WASHER It is recommended that suitable gate stops are always fitted to the system both in open and close gate positions. The gate stop for open gate position is incorporated with the operator, both right-hand and left-hand. The gate stop covers are different being designed as handed units (part No. 2062=right-hand, 2055=left hand). Another feature of the incorporated open gate stop is the possibility of being adjusted to the required distance to achieve the required opening angle, either 90° or more/less. PIC. 5 GATE LEAF OVERTURN LEVEL ARTICULATED ARM OPERATOR COVER PIC. 3 Rh Fix the bracket to the pillar and bring the electric cable to the most suitable position so that the fixing of the articulated arm is allowed to coincide with a solid crossing bar of the gate leaf. The shoe bracket is to be bolted or welded to the gate at a suitable distance which is set after the first manual tests. (Release lever B page 10) BOTH Rh AND Lh Lh DISTANCE The distance from gate pivot center to arm bolt center is to be calculated through manual operations of the gate before fixing the shoe bracket. The distances on page 6-7 are merely an application example. RIGHT-HAND ARTICULATED ARM LEFT-HAND ARTICULATED ARM GRUB SCREW GRUB SCREW SQUARE SECTION SHAFT COMPLETELY INSTALLED UNIT. LEFT-HANDED MODEL ANTI-CRUSH DESIGN ARTICULATED ARM FOR SAFETY ELECTRIC MOTOR/HYDRAULIC JACK ASSEMBLY REFERENCE SEAT PIC. 6 PIC. 4 APROLI 280 BATT is easy to install. It can be supplied either fitted with hydraulic locking device for gates up to 2 m width, or without hydraulic locking with an electric lock for gate leaf up to 5 m. 4 Both right-hand and left-hand applications are possible just by turning over the articulated arm and fitting it to the square section shaft of the operator. Tighten the retaining pin in its seat to fix the arm to the shaft. The assembly ie. motor/jack, fixing bracket and cover are designed to suit both right and left-hand applications with the same method of installation. Important: the articulated arm must be fixed so that it pushes against the gates and keeps them well pressed on to the close position gate stop. 5 HOW TO FIX APROLI 280 BATT TO A PILLAR BY EXPANDING BOLTS OR SCREWS Before fitting the operator APROLI 280 BATT to the gate, make sure that the gate structure is adequate to be electrically operated and that is strong enough to bear the mechanical stress of automatic operations and is well built and smooth running. It is recommended to reinforce the gate and fix the metallic parts which may not work properly, do the necessary to prevent or correct friction of the gate against the pavement or pillar (this must particularly apply to the gate hinges). APPLICATION OF TWO APROLI 280 BATT ON TO A DOUBLE SWINGING GATE. 90° OPENING. The recommended maximum gate width with APROLI 280 is 5 m. The locking type operator is recommended up to 2 m gate width. Beyond 2 m a lock is required to be fitted to the gate and the non locking type operator is advisable. 2m VERY LARGE PILLAR WHERE THE GATE HINGE IS FIXED IN THE MIDDLE 2m LEFT-HAND ARTICULATED ARM RIGHT-HAND ARTICULATED ARM 4 EXPANDING BOLTS MAINS SUPPLY ELECTRIC CABLE LEFT-HAND GATE STOP IN OPEN GATE POSITION 90° GATE STOP IN CLOSE GATE POSITION RIGHT-HAND GATE STOP IN OPEN GATE POSITION 90° FIXING BRACKET NUTS WITH WASHER It is recommended that suitable gate stops are always fitted to the system both in open and close gate positions. The gate stop for open gate position is incorporated with the operator, both right-hand and left-hand. The gate stop covers are different being designed as handed units (part No. 2062=right-hand, 2055=left hand). Another feature of the incorporated open gate stop is the possibility of being adjusted to the required distance to achieve the required opening angle, either 90° or more/less. PIC. 5 GATE LEAF OVERTURN LEVEL ARTICULATED ARM OPERATOR COVER PIC. 3 Rh Fix the bracket to the pillar and bring the electric cable to the most suitable position so that the fixing of the articulated arm is allowed to coincide with a solid crossing bar of the gate leaf. The shoe bracket is to be bolted or welded to the gate at a suitable distance which is set after the first manual tests. (Release lever B page 10) BOTH Rh AND Lh Lh DISTANCE The distance from gate pivot center to arm bolt center is to be calculated through manual operations of the gate before fixing the shoe bracket. The distances on page 6-7 are merely an application example. RIGHT-HAND ARTICULATED ARM LEFT-HAND ARTICULATED ARM GRUB SCREW GRUB SCREW SQUARE SECTION SHAFT COMPLETELY INSTALLED UNIT. LEFT-HANDED MODEL ANTI-CRUSH DESIGN ARTICULATED ARM FOR SAFETY ELECTRIC MOTOR/HYDRAULIC JACK ASSEMBLY REFERENCE SEAT PIC. 6 PIC. 4 APROLI 280 BATT is easy to install. It can be supplied either fitted with hydraulic locking device for gates up to 2 m width, or without hydraulic locking with an electric lock for gate leaf up to 5 m. 4 Both right-hand and left-hand applications are possible just by turning over the articulated arm and fitting it to the square section shaft of the operator. Tighten the retaining pin in its seat to fix the arm to the shaft. The assembly ie. motor/jack, fixing bracket and cover are designed to suit both right and left-hand applications with the same method of installation. Important: the articulated arm must be fixed so that it pushes against the gates and keeps them well pressed on to the close position gate stop. 5 20 mm FROM PILLAR 40 SURFACE LINE EXAMPLE OF APPLICATIONS TO PILLARS OF VARIOUS DIMENSIONS. DISTANCES ARE NOT BINDING AND ARE QUOTED FOR REFERENCE ONLY GATE STOP IN CLOSED POSITION 510 GATE STOP IN CLOSED POSITION CLOSED GATE LEAF APPLICATION EXAMPLE 700x700 mm PILLAR 3 m GATE LEAF - 130 Kg ELECTRIC LOCK 170 APPLICATION EXAMPLE 400x400 mm PILLAR 2 m GATE LEAF - 110 Kg 20 mm FROM PILLAR 40 SURFACE LINE 20 mm FROM PILLAR 40 SURFACE LINE CLOSED GATE LEAF 460 40 580 90 APPLICATION EXAMPLE 800x800 mm PILLAR 4 m GATE LEAF - 140 Kg 170 OPEN GATE LEAF 100° 40 OPEN GATE LEAF 100° 20 mm FROM PILLAR SURFACE LINE 560 20 mm FROM PILLAR 40 SURFACE LINE 650 PIC. 11 PIC. 8 GATE STOP IN CLOSED POSITION CLOSED GATE LEAF 900x900 90 46 0 58 0 90 300 ELECTRIC LOCK GATE STOP IN CLOSED POSITION ELECTRIC LOCK 450 600x600 CLOSED GATE LEAF GATE STOP IN CLOSED POSITION ELECTRIC LOCK 400 250 CLOSED GATE LEAF GATE STOP IN CLOSED POSITION 90 APPLICATION EXAMPLE 500x500 mm PILLAR 3 m GATE LEAF - 100 Kg 620 PIC. 10 560 500x500 PIC. 7 100° 800x800 OPEN GATE LEAF 100° OPEN GATE LEAF 40 580 460 90 90 200 350 CLOSED GATE LEAF 700X700 400x400 20 mm FROM PILLAR 40 SURFACE LINE 560 APPLICATION EXAMPLE 900x900 mm PILLAR 5 m GATE LEAF - 150 Kg 170 60 100° OPEN GATE LEAF APPLICATION EXAMPLE 600x600 mm PILLAR 1.8 m GATE LEAF - 140 Kg OPEN GATE LEAF 100° PIC. 12 PIC. 9 6 It is recommended that all gates are provided with adequate gate stops both in open and closed gate positions. When a 5 m gate is involved the weight must not be greater than 200 Kg and it is required to fit the gate with an electric lock, the operator must be non locking type. With gates up to 2 m width, it is possible to install the locking type without electric lock. See the examples and drawings on pages 6 - 7. 7 20 mm FROM PILLAR 40 SURFACE LINE EXAMPLE OF APPLICATIONS TO PILLARS OF VARIOUS DIMENSIONS. DISTANCES ARE NOT BINDING AND ARE QUOTED FOR REFERENCE ONLY GATE STOP IN CLOSED POSITION 510 GATE STOP IN CLOSED POSITION CLOSED GATE LEAF APPLICATION EXAMPLE 700x700 mm PILLAR 3 m GATE LEAF - 130 Kg ELECTRIC LOCK 170 APPLICATION EXAMPLE 400x400 mm PILLAR 2 m GATE LEAF - 110 Kg 20 mm FROM PILLAR 40 SURFACE LINE 20 mm FROM PILLAR 40 SURFACE LINE CLOSED GATE LEAF 460 40 580 90 APPLICATION EXAMPLE 800x800 mm PILLAR 4 m GATE LEAF - 140 Kg 170 OPEN GATE LEAF 100° 40 OPEN GATE LEAF 100° 20 mm FROM PILLAR SURFACE LINE 560 20 mm FROM PILLAR 40 SURFACE LINE 650 PIC. 11 PIC. 8 GATE STOP IN CLOSED POSITION CLOSED GATE LEAF 900x900 90 46 0 58 0 90 300 ELECTRIC LOCK GATE STOP IN CLOSED POSITION ELECTRIC LOCK 450 600x600 CLOSED GATE LEAF GATE STOP IN CLOSED POSITION ELECTRIC LOCK 400 250 CLOSED GATE LEAF GATE STOP IN CLOSED POSITION 90 APPLICATION EXAMPLE 500x500 mm PILLAR 3 m GATE LEAF - 100 Kg 620 PIC. 10 560 500x500 PIC. 7 100° 800x800 OPEN GATE LEAF 100° OPEN GATE LEAF 40 580 460 90 90 200 350 CLOSED GATE LEAF 700X700 400x400 20 mm FROM PILLAR 40 SURFACE LINE 560 APPLICATION EXAMPLE 900x900 mm PILLAR 5 m GATE LEAF - 150 Kg 170 60 100° OPEN GATE LEAF APPLICATION EXAMPLE 600x600 mm PILLAR 1.8 m GATE LEAF - 140 Kg OPEN GATE LEAF 100° PIC. 12 PIC. 9 6 It is recommended that all gates are provided with adequate gate stops both in open and closed gate positions. When a 5 m gate is involved the weight must not be greater than 200 Kg and it is required to fit the gate with an electric lock, the operator must be non locking type. With gates up to 2 m width, it is possible to install the locking type without electric lock. See the examples and drawings on pages 6 - 7. 7 ON TO “0” THE DELAY IS OUT OF SERVICE st 1 CHANNEL 24 V OUTPUT 70 LEAF DELAY TIMER CLOSE +DWELL TIME 3 4 1 2 3 4 5 RUN + MOTOR OPEN & CLOSE TIME 4 CAPACITORS 12,5µF 6 5 6 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 COMMON ELECTRIC MOTORS SINGLE-PHASE 230 V SINGLE-PHASE SUPPLY VOLTAGE LED No. 1 - It switches on when voltage is supplied SAFETY CONTACT N.C. ALL OPERATIONS OPEN, CLOSE AND REVERSE RADIO CONTACT Max permitted load: 2 pairs photocells 1 radio receiver 8 24 V OUTPUT A.C. PULSE TWICE CONSECUTIVELY TO OPEN BOTH GATE LEAFS 24 V INDICATOR - 3 W max. VOLTAGE OUTPUT ELECTRIC LOCK SUPPLY COMMON RADIO CONTACT N.O. STOP SWITCH N.C. CONTACT CLOSE SWITCH N.O. CONTACT OPEN SWITCH N.O. CONTACT COMMON N.C. CONTACT PHOTOCELLS 7 M2 230 V FLASHING LAMP 25 W max. = PHOTOCELLS 2nd PAIR = Inside photocells N.C. contact If obstracted, they prevent the gates from opening reverse gate direction during close cycle Should more pairs of photocells be required than the recommended quantity, fit an auxiliary transformer outside the control box. M1 PEDESTRIAN MODE ONE PULSE OPENS ONE GATE LEAF ONLY 5 10 7 OFF 4 3 COMMON 1 2 3 4 5 6 7 8 2 230 Volt MAINS SWITCH 1 AMP. FUSE 24 V OUTPUT TERMINALS 12-13 12,5µF 1 2 FLASHING LAMP 630 mA FUSE FUSE 5 AMPS 9 ON 3 + — 8 DIP-SWITCH B FUSE 630 mA MICROPROCESSOR TERMINAL FOR CONNECTIONS TO PUSH BUTTONS PULIN 3 ON 1 TIMER SWITCHES RADIO CONTROL PLUG-IN CARD SUPPORT 26 27 28 The below diagram is general for an application of the operator and the complementary accessories which are supplied with the unit. 13 exp CONNECTION DIAGRAM FOR SWING GATES 11 15 12 16 13 6 NOTE WELL: For special applications, ie. to switch on lights - CCTV etc., SOLID STATE RELAYS are recommended to be used only. Standard relays would affect the micro-processor. NOTE WELL: THIS PANEL IS TESTED TO OPERATE GATES ONLY THROUGH FADINI ACCESSORIES. NO GUARANTEE FOR ACCESSORIES OF OTHER MAKE OR SPECIAL APPLICATIONS. Drwg. No. 14 7 6 8 17 1643 P.C. BOARD 9 ALL THE ELECTRICAL EQUIPMENT MUST BE EARTH CONNECTED ELECTRICAL WIRING DIAGRAM OF THE ELECTRONIC PROGRAMMER PIC. 13 OPEN CLOSE The 6 LEDs on the P.C. board indicate the following: Led No. 1 It switches on when voltage is supplied Led No. 2 Photocells - Normally on. It switches off when the photocells are obstructed Led No. 3 Open - It switches on when the respective switch is activated Led No. 4 Close - It switches on when the respective switch it activated Led No. 5 Stop - Normally on. it switches off when the respective switch is activated Led No. 6 Radio - It switches on whenever a pulse is given, either from remote control, keyswitch or push buttons. TERMINAL BOARD STOP STOP N.C. CONTAC CLOSE N.O. CONTACT OPEN N.O. CONTACT COMMON E. CONNECTIONS KEYSWITCH SECH 15 To perform the electrical work, connections are as per diagrams on pages 8-9. Once the connections have been made, adjust the switches in the control box so that the sequence of operations occurs as pre-set. Set DIP switch 3 on automatic and check if the working times meet your requirements. On semiautomatic mode, one pulse opens the gates, a second pulse is needed to close the gates. Sx 2° Dx 1° PLEASE NOTE: Should the electric motors fail to start properly because of power shortage, connect some extra 12.5 µF capacitors to the phase and common terminals as shown in pic. 16. Terminal board Elpro 13 exp 16 17 18 19 20 21 22 23 Drwg. No. 1643 12.5 µF PIC. 14 8 PHASE M2 CONNECTION TO THE “PULIN 3” PUSH BUTTONS WITH STATUS INDICATION LEDS. PHASE M2 CLOSE 9 - RADIO TRANSMITTER TYPE A43/ 2TR 10 - KEYSWITCH TYPE SECH 15 11 - ELECTRIC LOCK 12 - PHOTOCELL TRANSMITTER DIFO 33. OUTSIDE 13 - RIGHT-HAND OPERATOR TYPE APROLI 280 BATT 14 - PHOTOCELL RECEIVER TYPE DIFO 33 OUTSIDE 15 - LEFT-HAND OPERATOR TYPE APROLI 280 BATT 16 - MECHANICAL LATCH 17 - POST WITH PHOTOCELL PROJECTOR TYPE DIFO 33 COMMON M2 STOP N.O. 1 - STEMMED AERIAL A 43 2 - LAPI 2 FLASHING LAMP 3 - 230 V - 50/60 Hz MAINS SWITCH WITH MAGNETIC-THERMAL DIFFERENTIAL TYPE 0.03 A (beyond 100 m distance 2.5 mm Ø cables are recommended) 4 - RADIO RECEIVER CARD A 43/2R 5 - ELECTRONIC PROGRAMMER TYPE ELPRO 13 exp 6 - JUNCTION BOX 7 - WALL PUSH BUTTONS PULIN 3 (INSIDE HOME) 8 - POST WITH PHOTOCELL RECEIVER TYPE DIFO 33 PHASE M1 OPEN N.C. Once the connections have been made, do the first switching test through the control panel. Set the motor run timer so that the motor is allowed to run 4 - 5 seconds more than the gates. Set the other timers to meet the site requirements. Set DIP switch B No. 3 to automatic (ON): on pulsing to 4 - 8 the gates must be operated as pre-set, ie. opening and only after the dwell time, closing. Adjust the times through the respective timers. (See No. 07, 08 and 09 drwg. No. 1643). With DIP switch "B" No. 3 to semiautomatic (OFF) one pulse opens the gates, a second pulse to 5 - 8 is needed to close the gates. Any one pulse to 7 - 8 will open, close or reverse the gates independently from the operation being performed. It is recommended to carefully read the instructions in the control box to have all the functions performed correctly. PHASE M1 N.O. 26 27 28 3 6 COMMON M1 5 COMMON 4 COMMON 3 PIC. 15 PIC. 16 9 12.5 µF ON TO “0” THE DELAY IS OUT OF SERVICE st 1 CHANNEL 24 V OUTPUT 70 LEAF DELAY TIMER CLOSE +DWELL TIME 3 4 1 2 3 4 5 RUN + MOTOR OPEN & CLOSE TIME 4 CAPACITORS 12,5µF 6 5 6 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 COMMON ELECTRIC MOTORS SINGLE-PHASE 230 V SINGLE-PHASE SUPPLY VOLTAGE LED No. 1 - It switches on when voltage is supplied SAFETY CONTACT N.C. ALL OPERATIONS OPEN, CLOSE AND REVERSE RADIO CONTACT Max permitted load: 2 pairs photocells 1 radio receiver 8 24 V OUTPUT A.C. PULSE TWICE CONSECUTIVELY TO OPEN BOTH GATE LEAFS 24 V INDICATOR - 3 W max. VOLTAGE OUTPUT ELECTRIC LOCK SUPPLY COMMON RADIO CONTACT N.O. STOP SWITCH N.C. CONTACT CLOSE SWITCH N.O. CONTACT OPEN SWITCH N.O. CONTACT COMMON N.C. CONTACT PHOTOCELLS 7 M2 230 V FLASHING LAMP 25 W max. = PHOTOCELLS 2nd PAIR = Inside photocells N.C. contact If obstracted, they prevent the gates from opening reverse gate direction during close cycle Should more pairs of photocells be required than the recommended quantity, fit an auxiliary transformer outside the control box. M1 PEDESTRIAN MODE ONE PULSE OPENS ONE GATE LEAF ONLY 5 10 7 OFF 4 3 COMMON 1 2 3 4 5 6 7 8 2 230 Volt MAINS SWITCH 1 AMP. FUSE 24 V OUTPUT TERMINALS 12-13 12,5µF 1 2 FLASHING LAMP 630 mA FUSE FUSE 5 AMPS 9 ON 3 + — 8 DIP-SWITCH B FUSE 630 mA MICROPROCESSOR TERMINAL FOR CONNECTIONS TO PUSH BUTTONS PULIN 3 ON 1 TIMER SWITCHES RADIO CONTROL PLUG-IN CARD SUPPORT 26 27 28 The below diagram is general for an application of the operator and the complementary accessories which are supplied with the unit. 13 exp CONNECTION DIAGRAM FOR SWING GATES 11 15 12 16 13 6 NOTE WELL: For special applications, ie. to switch on lights - CCTV etc., SOLID STATE RELAYS are recommended to be used only. Standard relays would affect the micro-processor. NOTE WELL: THIS PANEL IS TESTED TO OPERATE GATES ONLY THROUGH FADINI ACCESSORIES. NO GUARANTEE FOR ACCESSORIES OF OTHER MAKE OR SPECIAL APPLICATIONS. Drwg. No. 14 7 6 8 17 1643 P.C. BOARD 9 ALL THE ELECTRICAL EQUIPMENT MUST BE EARTH CONNECTED ELECTRICAL WIRING DIAGRAM OF THE ELECTRONIC PROGRAMMER PIC. 13 OPEN CLOSE The 6 LEDs on the P.C. board indicate the following: Led No. 1 It switches on when voltage is supplied Led No. 2 Photocells - Normally on. It switches off when the photocells are obstructed Led No. 3 Open - It switches on when the respective switch is activated Led No. 4 Close - It switches on when the respective switch it activated Led No. 5 Stop - Normally on. it switches off when the respective switch is activated Led No. 6 Radio - It switches on whenever a pulse is given, either from remote control, keyswitch or push buttons. TERMINAL BOARD STOP STOP N.C. CONTAC CLOSE N.O. CONTACT OPEN N.O. CONTACT COMMON E. CONNECTIONS KEYSWITCH SECH 15 To perform the electrical work, connections are as per diagrams on pages 8-9. Once the connections have been made, adjust the switches in the control box so that the sequence of operations occurs as pre-set. Set DIP switch 3 on automatic and check if the working times meet your requirements. On semiautomatic mode, one pulse opens the gates, a second pulse is needed to close the gates. Sx 2° Dx 1° PLEASE NOTE: Should the electric motors fail to start properly because of power shortage, connect some extra 12.5 µF capacitors to the phase and common terminals as shown in pic. 16. Terminal board Elpro 13 exp 16 17 18 19 20 21 22 23 Drwg. No. 1643 12.5 µF PIC. 14 8 PHASE M2 CONNECTION TO THE “PULIN 3” PUSH BUTTONS WITH STATUS INDICATION LEDS. PHASE M2 CLOSE 9 - RADIO TRANSMITTER TYPE A43/ 2TR 10 - KEYSWITCH TYPE SECH 15 11 - ELECTRIC LOCK 12 - PHOTOCELL TRANSMITTER DIFO 33. OUTSIDE 13 - RIGHT-HAND OPERATOR TYPE APROLI 280 BATT 14 - PHOTOCELL RECEIVER TYPE DIFO 33 OUTSIDE 15 - LEFT-HAND OPERATOR TYPE APROLI 280 BATT 16 - MECHANICAL LATCH 17 - POST WITH PHOTOCELL PROJECTOR TYPE DIFO 33 COMMON M2 STOP N.O. 1 - STEMMED AERIAL A 43 2 - LAPI 2 FLASHING LAMP 3 - 230 V - 50/60 Hz MAINS SWITCH WITH MAGNETIC-THERMAL DIFFERENTIAL TYPE 0.03 A (beyond 100 m distance 2.5 mm Ø cables are recommended) 4 - RADIO RECEIVER CARD A 43/2R 5 - ELECTRONIC PROGRAMMER TYPE ELPRO 13 exp 6 - JUNCTION BOX 7 - WALL PUSH BUTTONS PULIN 3 (INSIDE HOME) 8 - POST WITH PHOTOCELL RECEIVER TYPE DIFO 33 PHASE M1 OPEN N.C. Once the connections have been made, do the first switching test through the control panel. Set the motor run timer so that the motor is allowed to run 4 - 5 seconds more than the gates. Set the other timers to meet the site requirements. Set DIP switch B No. 3 to automatic (ON): on pulsing to 4 - 8 the gates must be operated as pre-set, ie. opening and only after the dwell time, closing. Adjust the times through the respective timers. (See No. 07, 08 and 09 drwg. No. 1643). With DIP switch "B" No. 3 to semiautomatic (OFF) one pulse opens the gates, a second pulse to 5 - 8 is needed to close the gates. Any one pulse to 7 - 8 will open, close or reverse the gates independently from the operation being performed. It is recommended to carefully read the instructions in the control box to have all the functions performed correctly. PHASE M1 N.O. 26 27 28 3 6 COMMON M1 5 COMMON 4 COMMON 3 PIC. 15 PIC. 16 9 12.5 µF The two safety pressure valves are identified by colours: “A” open is red; “C” close is green. They are located in the front of the motor/pump unit, easy to reach for setting operations in order to meet the power requirements Pic. 17. Once the valves are set, you can fit the cover and the other accessories. RELEASE BY 1 TURN TO LET THE AIR OUT OF OIL RESERVOIR APROLI 280 BATT SPECIAL VERSION CODE 287 The flow regulator has the purpose of mantaining constant the rotation speed of the shaft that operates the articulated arm. SPEED FLOW REGULATOR OPEN SPEED SPEED “S” PIC. 18 “S” LESS POWER OIL FADINI A 15 BY AGIP ® 404 TECHNICAL SPECIFICATIONS FIXING BRACKET BATT OIL-HYDRAULIC s.n.c. Via Mantova, 177/A - 37053 Cerea (VR) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054 “C” 402 260 THIS STICKER IS FITTED ON THE OIL RESERVOIR “A” W 250 HP 0.25 VOLTS 230 A 1.2 r.p.m. 1˙350 Hz 50 Nm 196.2 µF 12.5 100 ELECTRIC MOTOR/ JACK ASSEMBLY Degree of protection IP 555 345 290 MOTOR 2 PHASE 106 190 MAXIMUM PRESSURE VALVE “OPEN” RED IN COLOUR SPEED RELEASE IMPORTANT AFTER INSTALLING BY 1 TURN APROLI 280 BATT AIR BLEED MAXIMUM PRESSURE VALVE “CLOSE” GREEN IN COLOUR CONSTANT SPEED FLOW REGULATOR CLOSE MORE POWER Working pressure max. 3 MPa (30 Bars) EARTH 190 OIL FADINI A15 BY AGIP MADE IN ITALY 240 20x20 407 139 35 “B” RELEASE LEVER 50 PROTECTION COVER 520 PULL THE LEVER DOWNWARDS TO RELEASE 218 570 580 460 PIC. 17 The setting of the safety pressure valves is to be done so to achieve the exact amount of power required to safely operate the gate. The more you turn the screw clockwise, the more you increase the power of the operator. Please note, once APROLI 280 has been fixed, unscrew the air bleed screw by one turn. This screw is fitted on the cap of the oil reservoire, where the mains cable is led to the motor. Should the operator “APROLI 280” be removed for maintenance or repairing, tighten the screw "S" to prevent oil from coming out during handling. In case of power failure, to open the two leafs fitted with APROLI 280 BATT non-loking type, you have to release the electric lock with the key and push the gate leafs open by hand in a very smooth way. Should the operator be fitted with locking device, first pull the release lever "B" downwards and then push open (Pic. 17). Open the hinged door to have access to the lever. NEVER CUT THE ELECTRIC CABLES - Please note that the electric cables must be removed from their terminals by loosening the fastening screws. Never cut the electric cables. Also make sure that the 230V mains switch No. 3 is off before removing the cables. See page 9, pic. 15. - Only by keeping to these fitting instructions it can be achieved a reliable installation and the best performance of the operator. The installation is fully under the responsability of the installation agent, even if it consists entirelly of Fadini products as listed in this booklet. It is advisable that the system is installed in full compliance with these instructions and in observance of the existing laws which rule automatic doors. - All the information, specifications and drawings contained herein are subject to any change that is considered appropriate by the manufacturer with any previous notice. 10 LEFT-HAND ARTICULATED ARM WITH RETAINING SCREW AND SHOE 580 520 Lh 460 570 TURN IT OVER TO MAKE IT RIGHT-HAND RIGHT-HAND ARTICULATED ARM WITH RETAINING SCREW AND SHOE Rh PIC. 19 HYDRAULIC PUMP ELECTRIC MOTOR Pump flow rate - P3 ...........................................................0.85 l/min. Working pressure ....................................................1 MPa (10 bars) Max. pressure...........................................................3 MPa (30 bars) Working temperature ....................................................–20°C +80°C Opening time..................................................................................23 s Oil type ..............................................................A 15 FADINI by AGIP Max. shaft rotation angle............................................................205° Rated torque .........................................................................196.2 Nm Static weight of operator ..........................................................11 Kg IP Standards...............................................................................IP 555 Power output .........................................................0.18 KW (0.25 HP) Supply voltage / Frequency .........................................230 V - 50 Hz Absorbed current ........................................................................1.2 A Absorbed power........................................................................250 W Capacitor...................................................................................12.5 µF Motor rotation speed.......................................................1˙350 r.p.m. Intermittent service........................................................................S 3 Duty cycle ................23 sec. Open - 30 sec. Dwell - 23 sec. Close Time of one complete cycle ........................................................76 s No. of complete cycles Open - Dwell - Close ....................47/hour No. cycles a year, 8 hours a day ..........................................137˙000 11 The two safety pressure valves are identified by colours: “A” open is red; “C” close is green. They are located in the front of the motor/pump unit, easy to reach for setting operations in order to meet the power requirements Pic. 17. Once the valves are set, you can fit the cover and the other accessories. RELEASE BY 1 TURN TO LET THE AIR OUT OF OIL RESERVOIR APROLI 280 BATT SPECIAL VERSION CODE 287 The flow regulator has the purpose of mantaining constant the rotation speed of the shaft that operates the articulated arm. SPEED FLOW REGULATOR OPEN SPEED SPEED “S” PIC. 18 “S” LESS POWER OIL FADINI A 15 BY AGIP ® 404 TECHNICAL SPECIFICATIONS FIXING BRACKET BATT OIL-HYDRAULIC s.n.c. Via Mantova, 177/A - 37053 Cerea (VR) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054 “C” 402 260 THIS STICKER IS FITTED ON THE OIL RESERVOIR “A” W 250 HP 0.25 VOLTS 230 A 1.2 r.p.m. 1˙350 Hz 50 Nm 196.2 µF 12.5 100 ELECTRIC MOTOR/ JACK ASSEMBLY Degree of protection IP 555 345 290 MOTOR 2 PHASE 106 190 MAXIMUM PRESSURE VALVE “OPEN” RED IN COLOUR SPEED RELEASE IMPORTANT AFTER INSTALLING BY 1 TURN APROLI 280 BATT AIR BLEED MAXIMUM PRESSURE VALVE “CLOSE” GREEN IN COLOUR CONSTANT SPEED FLOW REGULATOR CLOSE MORE POWER Working pressure max. 3 MPa (30 Bars) EARTH 190 OIL FADINI A15 BY AGIP MADE IN ITALY 240 20x20 407 139 35 “B” RELEASE LEVER 50 PROTECTION COVER 520 PULL THE LEVER DOWNWARDS TO RELEASE 218 570 580 460 PIC. 17 The setting of the safety pressure valves is to be done so to achieve the exact amount of power required to safely operate the gate. The more you turn the screw clockwise, the more you increase the power of the operator. Please note, once APROLI 280 has been fixed, unscrew the air bleed screw by one turn. This screw is fitted on the cap of the oil reservoire, where the mains cable is led to the motor. Should the operator “APROLI 280” be removed for maintenance or repairing, tighten the screw "S" to prevent oil from coming out during handling. In case of power failure, to open the two leafs fitted with APROLI 280 BATT non-loking type, you have to release the electric lock with the key and push the gate leafs open by hand in a very smooth way. Should the operator be fitted with locking device, first pull the release lever "B" downwards and then push open (Pic. 17). Open the hinged door to have access to the lever. NEVER CUT THE ELECTRIC CABLES - Please note that the electric cables must be removed from their terminals by loosening the fastening screws. Never cut the electric cables. Also make sure that the 230V mains switch No. 3 is off before removing the cables. See page 9, pic. 15. - Only by keeping to these fitting instructions it can be achieved a reliable installation and the best performance of the operator. The installation is fully under the responsability of the installation agent, even if it consists entirelly of Fadini products as listed in this booklet. It is advisable that the system is installed in full compliance with these instructions and in observance of the existing laws which rule automatic doors. - All the information, specifications and drawings contained herein are subject to any change that is considered appropriate by the manufacturer with any previous notice. 10 LEFT-HAND ARTICULATED ARM WITH RETAINING SCREW AND SHOE 580 520 Lh 460 570 TURN IT OVER TO MAKE IT RIGHT-HAND RIGHT-HAND ARTICULATED ARM WITH RETAINING SCREW AND SHOE Rh PIC. 19 HYDRAULIC PUMP ELECTRIC MOTOR Pump flow rate - P3 ...........................................................0.85 l/min. Working pressure ....................................................1 MPa (10 bars) Max. pressure...........................................................3 MPa (30 bars) Working temperature ....................................................–20°C +80°C Opening time..................................................................................23 s Oil type ..............................................................A 15 FADINI by AGIP Max. shaft rotation angle............................................................205° Rated torque .........................................................................196.2 Nm Static weight of operator ..........................................................11 Kg IP Standards...............................................................................IP 555 Power output .........................................................0.18 KW (0.25 HP) Supply voltage / Frequency .........................................230 V - 50 Hz Absorbed current ........................................................................1.2 A Absorbed power........................................................................250 W Capacitor...................................................................................12.5 µF Motor rotation speed.......................................................1˙350 r.p.m. Intermittent service........................................................................S 3 Duty cycle ................23 sec. Open - 30 sec. Dwell - 23 sec. Close Time of one complete cycle ........................................................76 s No. of complete cycles Open - Dwell - Close ....................47/hour No. cycles a year, 8 hours a day ..........................................137˙000 11 Lineagrafica 280 BATT WARNINGS - It is recommended to keep to the instructions here outlined - check the specifications on the motor sticker with your mains supply. - Dispose properly of the packaging: cardboard, nylon, polystyrene, through specializing companies. - Should the operator be removed, do not cut the electric cable. This must be properly removed from the terminal board in the junction box. - Switch off the mains switch before removing the junction box cover where the electric cable of APROLI 280 BATT is terminated. - All the system must be earthed by using the yellow/green wire, marked by its specific symbol. - It is recommended to read the regulations, suggestions and remarks quoted in the booklet "Warnings". - Should APROLI 280 BATT be removed for maintenance, servicing or repair, tighten the air bleeding screw to prevent oil coming out of the reservoir during transport. Meccanica Fadini recommends the control panel ELPRO 13 CEI to achieve an installation that is in conformity to the existing safety standards. The electronic programmer ELPRO 13 incorporates and can provide all the functions which are required by the most demanding applications with swinging gates. In addition to the standard features of a conventional control box type ELPRO 9 (see page 8 pic. 13) the following requirements can be provided: “stroke reversing pulse”, pedestrian mode, stop in any gate position by holding down the remote control button. Among the added features and improvements of ELPRO 13 in conformity to the European safety standards, there is the mains rotary switch: it is fitted to the box cover and switches off the mains voltage whenever the cover is removed. 3-2003 APROLI STATIC GATE WEIGHT 400 Kg each leaf 13 CEI SINGLE-PHASE l apricancel lo CUT OFF MAINS SWITCH The “CE” mark certifies that the operator conforms to the essential requirements of the European Directive art. 10 EEC 73/23, in relation to the manufacturer’s declaration for the supplied items, in compliance with the body of the regulations ISO 9000= UNI EN 29000. Automation in conformity to EN 12453, EN 12445 safety standard. The growth of MECCANICA FADINI has always been based on the development of guaranteed products thanks to our “TOTAL QUALITY CONTROL” system which ensures constant quality standards, updated knowledge of the European Standards and compliance with their requirements, in view of an ever increasing process of improvement. EUROPEAN MARK CERTIFYING CONFORMITY TO THE ESSENTIAL REQUIREMENTS OF THE STANDARDS 98/37 EC • DECLARATION OF CONFORMITY • GENERAL WARNINGS • EN 12453, EN 12445 STANDARDS • CEI EN 60204-1 STANDARDS • WARRANTY CERTIFICATE ON THE CUSTOMER’S REQUEST ® Made in Italy GB ® s.n.c. AUTOMATIC GATE MANUFACTURERS Distributor’s box The manufacturers reserve the right to change the products without any previous notice Via Mantova, 177/A - 37053 Cerea (Verona) Italy - Tel. 0442 330422 r.a. - Fax 0442 331054 - e-mail: info@fadini.net - www.fadini.net INSTALLATION MANUAL ®