Download technical installation manual vers. 13

Transcript
ingenium
www.ingeniumsl.com
accessories
➡ Cable BUSing®
➡ Cable BUSing®
Cable voltage
Cable for connecting BUSing® data bus
Installation
Allows devices communication and power supply.
It is important to follow a colours code
for the BUS.
• Flexible and shielded cable 2x0.5mm + 4x0.22mm
halogen free
• Operating temperature: –15 to +70ºC
The BUSing® protocol bus line has 4 wires
of which two are used for power and two
for data.
Red +12V
Yellow
A
Green
B
Black
Ref
V+Ð = 10Ð16Vcc
VAÐRef = 2.8Vcc aprox. (> VBÐRef)
VBÐRef = 2.6Vcc aprox. (< VAÐRef)
• Fire behaviour: no flame retardant, fire retardant, halogen
free, low emission of opaque smoke and fumes.
Screw terminal
• Outer diameter: 6.20mm (approx.)
Cable BUSing¨
Description
BUS cable supplied by Ingenium has 6 wires
(2x0.50mm + 4x0.22mm):
• 4 wires can be used for power supply
and two for data.
• Of the 4 used for supply, 2 are for +12 V DC and the
other 2 for reference or mass.
The maximum distance supported by the communication
bus between two devices is approximately 300 meters. It
should consider the voltage drop in the cable for power supplies if needed. The maximum bus distance should not exceed 1000 meters.
Pipeline of low voltage lines (bus and inputs) should be in a
different hose than supply (230V AC) and outputs (according
to RBT).
Red
S=0.50mm2
+12V
Red
S=0.22mm2
+12V
Yellow
S=0.22mm2
A
Green
S=0.22mm2
B
Black
S=0.22mm2
Ref
Black
S=0.50mm2
Ref
Crimp connector
Cable BUSing¨
Red
S=0.22mm2
Yellow
S=0.22mm2
A
Green
S=0.22mm2
B
Balack
S=0.22mm2
Ref
+12V