Transcript
ingenium www.ingeniumsl.com accessories ➡ Cable BUSing® ➡ Cable BUSing® Cable voltage Cable for connecting BUSing® data bus Installation Allows devices communication and power supply. It is important to follow a colours code for the BUS. • Flexible and shielded cable 2x0.5mm + 4x0.22mm halogen free • Operating temperature: –15 to +70ºC The BUSing® protocol bus line has 4 wires of which two are used for power and two for data. Red +12V Yellow A Green B Black Ref V+Ð = 10Ð16Vcc VAÐRef = 2.8Vcc aprox. (> VBÐRef) VBÐRef = 2.6Vcc aprox. (< VAÐRef) • Fire behaviour: no flame retardant, fire retardant, halogen free, low emission of opaque smoke and fumes. Screw terminal • Outer diameter: 6.20mm (approx.) Cable BUSing¨ Description BUS cable supplied by Ingenium has 6 wires (2x0.50mm + 4x0.22mm): • 4 wires can be used for power supply and two for data. • Of the 4 used for supply, 2 are for +12 V DC and the other 2 for reference or mass. The maximum distance supported by the communication bus between two devices is approximately 300 meters. It should consider the voltage drop in the cable for power supplies if needed. The maximum bus distance should not exceed 1000 meters. Pipeline of low voltage lines (bus and inputs) should be in a different hose than supply (230V AC) and outputs (according to RBT). Red S=0.50mm2 +12V Red S=0.22mm2 +12V Yellow S=0.22mm2 A Green S=0.22mm2 B Black S=0.22mm2 Ref Black S=0.50mm2 Ref Crimp connector Cable BUSing¨ Red S=0.22mm2 Yellow S=0.22mm2 A Green S=0.22mm2 B Balack S=0.22mm2 Ref +12V