Download CC-Link System Master/Local Module User's Manual
Transcript
11 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MELSEC-Q 11.3 Setting the Local Station Parameters This section explains the settings of the network parameters and the automatic refresh parameters of the local station. 11.3.1 Setting the network parameters of the local station (1) Setting the network parameters Set the network parameters as follows using the attached parameter setting checklist. Item Start I/O No. Operational setting Type Setting range 0000 to 0FE0 Setting value 0000 Data link disorder station setting Input data hold/clear Default: Clear Number of occupied stations Occupied 1 to 4 stations Default: Occupied 1 station Master station Master station (Duplex function) Local station Standby master station Default: Master station Hold / Clear Occupied 4 stations Master station Master station (Duplex function) Local station Standby master station Mode Online (Remote net mode) Online (Remote I/O net mode) Offline Default: Online (Remote net mode) All connect count 1 to 64 Default: 64 Remote input (RX) Device name: Select from X, M, L, B, D, W, R or ZR Remote output (RY) Device name: Select from Y, M, L, B, T, C, ST, D, W, R or ZR Remote register (RWr) Device name: Select from M, L, B, D, W, R or ZR Remote register (RWw) Device name: Select from M, L, B, T, C, ST, D, W, R or ZR Special relay (SB) Device name: Select from M, L, B, D, W, R, SB or ZR Special register (SW) Device name: Select from M, L, B, D, W, R, SW or ZR Retry count 1 to 7 Default: 3 times Automatic reconnection station count 1 to 10 Default: 1 module Online (Remote net mode) Online (Remote I/O net mode) Offline module Blank, 1 to 64 (Blank: No standby master station Standby master station No. specified) Default: Blank PLC down select Stop/continue Default: Stop Scan mode settings Asynchronous/synchronous Default: Asynchronous Delay information setting 0 to 100 (0: Not specified) Default: 0 11 - 6 Stop/continue Asynchronous/synchronous 11 - 6