Download 20-COMM-E EtherNet/IP Adapter User Manual
Transcript
6-20 Using Explicit Messaging ControlLogix – Formatting a Message to Read a Single Parameter (all versions) Figure 6.23 Get Attribute Single Message Configuration Screens The following table identifies the data that is required in each box to configure a message to read a single parameter. Configuration Tab Message Type Service Type (1) Service Code (1) Class Instance (2) Attribute Destination Communication Tab Path (3) Tag Tab Name Example Value CIP Generic Get Attribute Single e (Hex.) 93 or 9F (Hex.) (4) 3 (Dec.) 9 (Hex.) Output_Current (5) Example Value My_PowerFlex_Drive Example Value Single_Read_Message Description Used to access the Parameter Object in the adapter. This service is used to read a parameter value. Code for the requested service. Class ID for the DPI Parameter Object. Instance number is the same as parameter number. Attribute number for the Parameter Value attribute. The tag where the data that is read is stored. Description The path is the route that the message will follow. Description The name for the message. (1) The default setting for Service Type is “Custom,” enabling entry of a Service Code not available from the Service Type pull-down menu. When choosing a Service Type other than “Custom” from the pull-down menu, an appropriate Hex. value is automatically assigned to the Service Code box which is dimmed (unavailable). (2) The instance is the parameter number in the drive (Port 0). For example, to read parameter 4 of a peripheral in Port 5 of a PowerFlex 750-Series drive, the instance would be 21504 + 4 = 21508. See DPI Parameter Object on page C-16 (Class code 0x93) or Host DPI Parameter Object on page C-30 (Class code 0x9F) to determine the instance number. (3) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder. (4) See Table 6.A on page 6-2 for limitations of PowerFlex 7-Class and PowerFlex 750-Series drives when using DPI Parameter Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging. (5) In this example, Output Current is a 32-bit parameter requiring the Data Type field to be set to “DINT” when creating the controller tag. If the parameter being read is a 16-bit parameter, the tag Data Type field must be set to “INT.” When using a PowerFlex 700S or PowerFlex 750-Series drive, Output Current is a floating point number requiring the Data Type field to be set to “REAL” when the creating controller tag. See the drive documentation to determine the size of the parameter and its data type (16-bit or 32-bit integer or REAL). 20-COMM-E EtherNet/IP Adapter User Manual Publication 20COMM-UM010E-EN-P