Using Explicit Messaging
ControlLogix – Formatting a Message to Read a Single Parameter (all versions)
Figure 6.23 Get Attribute Single Message Configuration Screens
The following table identifies the data that is required in each box to
configure a message to read a single parameter.
Configuration Tab
Message Type
Service Type (1)
Service Code (1)
Class
Instance (2)
Attribute
Destination
Communication Tab
Path (3)
Tag Tab
Name
Example Value
CIP Generic
Get Attribute Single
e (Hex.)
93 or 9F (Hex.) (4)
3 (Dec.)
9 (Hex.)
Output_Current (5)
Example Value
My_PowerFlex_Drive
Example Value
Single_Read_Message
Description
Used to access the Parameter Object in the adapter.
This service is used to read a parameter value.
Code for the requested service.
Class ID for the DPI Parameter Object.
Instance number is the same as parameter number.
Attribute number for the Parameter Value attribute.
The tag where the data that is read is stored.
Description
The path is the route that the message will follow.
Description
The name for the message.
(1)
The default setting for Service Type is “Custom,” enabling entry of a Service Code not available from the Service Type
pull-down menu. When choosing a Service Type other than “Custom” from the pull-down menu, an appropriate Hex. value is
automatically assigned to the Service Code box which is dimmed (unavailable).
(2)
The instance is the parameter number in the drive (Port 0). For example, to read parameter 4 of a peripheral in Port 5 of a
PowerFlex 750-Series drive, the instance would be 21504 + 4 = 21508. See DPI Parameter Object on page C-16 (Class code
0x93) or Host DPI Parameter Object on page C-30 (Class code 0x9F) to determine the instance number.
(3)
Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder.
(4)
See Table 6.A on page 6-2 for limitations of PowerFlex 7-Class and PowerFlex 750-Series drives when using DPI Parameter
Object Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging.
(5)
In this example, Output Current is a 32-bit parameter requiring the Data Type field to be set to “DINT” when creating the
controller tag. If the parameter being read is a 16-bit parameter, the tag Data Type field must be set to “INT.” When using a
PowerFlex 700S or PowerFlex 750-Series drive, Output Current is a floating point number requiring the Data Type field to be
set to “REAL” when the creating controller tag. See the drive documentation to determine the size of the parameter and its
data type (16-bit or 32-bit integer or REAL).