c) Drain the vertical turbine pump motor oil to the minimum level as indicated in the sight glass. NOTE: Avoid
high-pressure transients as these can compromise Pump Station and irrigation system integrity.
d) Verify that the main station isolation valve from the Pump Station is shut.
e) Supply electrical power to the Pump Station by positioning the main power switch on the front of the
electrical cabinet to the ON position.
f ) Open taps that are furthest away from Pump Station and on the highest points.
g) Log-in to the touch-screen, enable only one (1) pump by pressing one of the buttons assigned to a pump at
the bottom of the touch-screen panel. The pump will start as system pressure should be less than set-point
pressure. NOTE: Keep the pressures at recommended value for each pump (See pre-installed value on the
Operator Panel).
h) Partially crack open the station isolation valve (while maintaining pressure).
i) When the whole Main Line is filled with water and pressurized, fully open the station isolation valve. NOTE:
Make sure all sprinklers are open to prime the lateral lines.
Pump Station User Manual - With E1071 Touch Screen
67