Specifications and Calibration
Default Alarms Settings
Sensor Range and Alarm Setpoints
The following table lists the factory alarm setpoints and sensor ranges.
Gas Detected
C2 H4
O
Ethylene oxide
(ETO)
Cl2
Chlorine
Range
Alarm A
Alarm B
Alarm C
0 - 20.4 ppm
1 ppm
5 ppm
18 ppm
0 -15.3 ppm
0.5 ppm
1 ppm
13.5 ppm
ClO2
Chlorine dioxide
0 - 2.5 ppm
0.1 ppm
0.3 ppm
0.9 ppm
CO
Carbon monoxide
0 - 255 ppm
25 ppm
200 ppm
225 ppm
Hydrogen sulfide
0 - 51 ppm
10 ppm
15 ppm
45 ppm
0 - 25.5 ppm
3 ppm
4 ppm
22.5 ppm
0 - 51 ppm
10 ppm
20 ppm
45 ppm
50% LEL
35 ppm
90% LEL
90 ppm
H2 S
LEL
NO
Hydrogen
chloride
Hydrogen
cyanide
Combustibles
Nitric oxide
NO2
Nitrogen dioxide
O2
Oxygen
SiH4
Silane
0 - 10.2 ppm
SO2
Sulfur dioxide
0 - 10.2 ppm
HCl
HCN
0 - 102% LEL 25% LEL
0 - 102 ppm 25 ppm
0 - 10.2 ppm 0.72 ppm
2 ppm
9 ppm
0 - 25.5% vol. 19.5% vol.
22% vol.
22.5% vol.
5 ppm
7 ppm
9 ppm
2 ppm
5 ppm
9 ppm
Latched Alarms
If alarms A, B, or C are set to latch, the LED (and applicable relays)
persist in the event of an alarm condition until the alarm is
acknowledged by placing the magnet over any of the keys and the
alarm condition is no longer present.
Note: Since Alarm C has no dedicated LED, both ALA and ALB LEDs
will blink for Alarm C.