2.3 INSTALLATION SITE
Failure to install dryer in the proper ambient conditions will affect the dryer’s ability to condense
refrigerant gas. This can cause higher loads on the compressor, loss of dryer efficiency and
performance, overheated condenser fan motors, electrical component failure and dryer failure due
to the following: compressor loss, fan motor failure and electrical component failure. Failures of
this type will affect warranty considerations.
Do not install dryer in an environment of corrosive chemicals, explosive gasses, poisonous
gasses; steam heat, areas of high ambient conditions or extreme dust and dirt.
In case of fire, use an approved fire extinguisher, water is not an acceptable means in cases of fire.
Minimum installation requirements:
• Select a clean dry area, free from dust, and
protected from atmospheric disturbances.
• The supporting area must be smooth, horizontal
and able to hold the weight of the dryer.
• Minimum ambient temperature +34 °F (+1 °C).
• Maximum ambient temperature +115 °F (+46 °C).
• Allow at least a clearance of 40in (1m) on each
side of the dryer for proper ventilation and to
facilitate eventual maintenance operations.
The dryer does not require attachment to the floor
surface; however installations where the unit is
suspended require an attachment to the hanging
apparatus.
Dryer ACT 20-75 hanging:
Dryer
ACT 20-75
A [in-mm]
B [in-mm]
C [in-mm]
D [in-mm]
1.9/16"- 40
14.3/16"- 360
3/4"- 20
13/16" - 30