CVent Termination Clearances
This appliance along with the CVent Common Vent System is certified with the Cvent 8-in Wall Termination Kit,
(790004) mounted in the orientation shown below.
The exhaust and combustion air terminations must
follow these clearances:
Horizontal Termination
[1] 12 inch minimum vertically from bottom of
combustion air termination to ground or anticipated
snow line.
Combustion
Air Vent
Min 36”
Exhaust
Vent
Min 36”
Combustion
Air Vent
[2] From edge of exhaust termination to edge of
combustion air termination:
Minimum of 36”
Maximum of 20’
[3] 36 inch minimum from multiple exhaust CVents
INTAKE IS NOT
ALLOWED WITHIN THE
SHADED AREA
Min 36”
Max 20’
Combustion
Air Vent
Combustion
Air Vent
There should be a minimum of 36” between exhaust
terminations in multiple common vent installations.
The vent (exhaust & combustion air) terminations to be
as specified in table in "Maximum Equivalent Vent
Length" Section above (model specific).
Combustion
Air Vent
Min 12” above grade or
anticipated snow level
NOTE: During colder weather when the exhaust temperature
is much hotter than the outside air, the exhaust
fumes condense producing water vapor. As a result
a plume of water vapor may be seen leaving the
exhaust.
EXHAUST
VENT
MAXIMUM 20’
MINIMUM 36”
COMBUSTION
AIR
VENT
Rinnai CVent
18