Download WRGA-01-ING GRAMEYER
Transcript
www.weg.net 6 IDENTIFICATION STICKER 1- Model 2- Power input 3- Rated current 4- Excitation voltage 5- Operation frequency The example above shows the main characteristics to be observed before installation. NOTE 1. The identification sticker is located under the regulator. 7 PROTECTIVE FUSE The fuse is used to limit the power supply input current to protect the generator field. The voltage regulators WRGA-01 are equipped with a controlled rectifier that forces the field voltage to obtain the correct generator output voltage. When operating with the maximum field voltage the power input current is a half of the field current. So, the fuse current must be a little more than the field voltage supported by the voltage regulator. Some fuse characteristics are listed bellow. Recommended manufacturer: LittelFuse (ordering code: 235003) Characteristics: Fast acting fuse. Dimensions: 5x20 mm. Current/Voltage: 3A/250V. Opening time: Fuse opening time % of maximum current Opening time 110 4 hours (minimum) 135 Max. 1 hour 200 Max 1 second 8 TRIMPOTS FUNCTION Vad: Voltage adjustment Stb: Stability Adjustment U/F: Under frequency adjustment U/F Drp: Droop adjustment (only for WRGA-01/C) 14 l Analog Voltage Regulator
This document in other languages
- español: WEG Analog voltage regulator WRGA-01
- português: WEG Analog voltage regulator WRGA-01