Download Motorcontroller CMMP…
Transcript
5. Sistema di sicurezza funzionale 5.2.2 Diagramma di timing STO "Safe Torque off" "Safe Torque off" Triggering of pulse amplifier supply relay (optocoupler driver) X3.Y.2 (24V) Timing for activation of "Safe Torque off" with safety switchgear PNOZ. 2. shut-down path X3.Y.2 (0V) t Supply of pulse amplifiers (optocoupler driver) “ON“ (15V) Discharge curve of electrolytic capacitors for the supply of the pulse amplifiers “OFF” t Floating feedback contact for driver supply (X3.Y.5/6) open closed t Output stage enabling (X1.Y, DIN4) “ON” Timing of output stage enabling variable 1. shut-down path “OFF” t Controller enabling (X1.Y, DIN5) t Internal output stage enabling (controlled by µP) “ON” “OFF” t Releasing motor holding brake (X6.Y.1/2) released (24V) Delay until brake is released! Can be set via Festo Configuration Tool „FCT“ fixed (0V) t Set speed "n" n Ramp can be set via Festo Configuration Tool „FCT“ n=0 “H” t Seven-segment display “H” “H” t tx t1 t2 t3 t4 t5 t6 t7 t8 t9 t10 t11 t12 t13 Fig. 5.2 Diagramma di timing per la funzione di sicurezza STO 52 Festo P.BE-CMMP-AS-C20-11A-IT 1010NH