Download RAN - RAL
Transcript
MANUALE DI ISTRUZIONI / INSTRUCTION MANUAL RADIATORI REMOTI / DRY COOLERS WORKING SPACE Indicated in fig. 3, minimum recommended distance to be left clear for a correct unit function and to allow access to the unit for maintenance. > 0,7 m >4m >1m >4m >1m Fig. 3.a.: HORIZONTAL AIR FLOW Fig. 3.b.: VERTICAL AIR FLOW INSTALL THE DRY COOLER IN A POSITION WHICH IS INACCESSIBLE TO UNAUTHORISED PERSONNEL: The heat exchanger fins are made from aluminium sheet which is only 0.1 mm thick and could cause cuts in the event of forceful accidental contact. N.B. the fan characteristic does not allow any ducting of the air flow. SIZE OF HYDRAULIC CONNECTIONS The dry cooler has male GAS connections. GAS connections. Female valves must be connected to the male gas connections (inlet/outlet) placing a seal between connections. NB: the diameter of the hydraulic line that connects the unit to its remote dry cooler (De) must be chosen according to the length of the hydraulic line itself. 1 ¼" male (0360-0510) 1 ½ " male (0700-0750) 2 " male (1000…2300) 3 " male (3600-5700) De Fig.4. Fig.5. RAN-RAL - Rev 1.1 25-07-08 IT - EN 22 (32)