INSTALLATION OF INDOOR UNIT
REFRIGERANT PIPING WORK
WARNING: The unit must be installated and maintained by licensed HVAC Technician.
SELECTION OF INSTALLATION LOCATION
CAUTIONS-NOT INSTALL UNIT AT
* Where cool air can be distributed throughout the room.
* Where condensation water is easily drained out.
* A place that can handle the weight of indoor unit.
* Not in laundry, nor in exhaust area.
* Where access for maintenance, is not blocked.
* Where there is too much of in the area.
* Where there is high levels of acid or acidity exists.
* Where there is electrical supply.
Select gas and liquid copper pipes per the following table.
MODEL
LIQOLID PIPE
GAS PIPE
WMMS-09EU-V2B(59)
1/4"
3/8"
WMMS-12EU-V2B(59)
1/4"
1/2"
WMMS-18EU-V2B(59)
1/4"
1/2"
WMMS-24EU-V2B(59)
1/4"
5/8"
Heat insulation layer
Connecting wire
Heat insulation layer
Gas pipe
Liquid pipe
Gas pipe and liquid pipe insulation must be no less than 3/8".
Pipe wrapping tape
Dia. drain pipe 1/2"
To keep dust and moisture out, both ends of copper
pipe must be fully covered, before putting insulation
on and coiling it.
In field installation, must check and keep the two ends of each copper pipe fully covered, to protect against any
foreign substances potentially entering the pipe and contaminating the refrigerant system.
INSTALLING LOCATION OPTIONS
* Ceiling
* Floor (Against wall, or stand alone)
* Unlock the return air grille by pressing the locking
latch shown at the right. Take out optional
accessories and access to wiring terminal.
* Unscrew to take off the side panel.
59.0"
or more
23.6"
or more
23.6"
or more
DRAIN PIPING WORK
39.4"
or more
11.8"
or more
(When drain hose is connected)
Drain piping
HANGING
In the case of ceiling hanging installation, there is no need to remove hanger bracket from the indoor unit.
Illustration as follows:
Celling slab
Buried hanging bolt
Incline the drain hose
BOLT
POSITION
INWARD
* The drain pipe connection can be either on the right
rear or right side.
Not to be lifted
* The inside diameter of the drain pipe should be
equal to or slightly bigger than the outside diameter
No folding
of the connecting pipe.
Not to be soaking in
* Keep the drain pipe as short as possible and incline
water
downwards at a gradient of at least 1/100 to
prevent air pockets.
Fig.1
* Use the drain hose and clamp that come with the
indoor unit. Insert the drain hose completely into the drain connector on the indoor unit. Tighten the clamp (Fig.2, 3).
* Not to fold drain hose (Fig.3).
*Wrap the sealing pad over the clamp and drain insulate to hose.
Hanger bracket
Air outlet
Tighten clamp
Rising
Carefully pour
water into
drain pan
Taping area
Drain hose
Fig.2
Fig.3
Fig.4
Check for smooth drainage after the piping work is done
* Pour water into the drain pan from the air outlet to check for smooth drainage (Fig.4).
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !
P15 OF 36
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !
P16 OF 36
INSTALLER'S
INSTRUCTION
INSTALLER'S
INSTRUCTION
Template
In selecting pipe running path, need to avoid as many bends as possible. If it is necessary, the bending radius
must be more than 1.5" or 2".
Connecting indoor unit
* Before connecting indoor unit, need to check if the indoor unit seals well. Dry nitrogen is loaded inside the indoor
unit before being packed at factory. If you hear the nitrogen gas blasting out of the broken seal, that means the
indoor unit is sealed. Otherwise, need to recharge with nitrogen and recheck. If you still don't hear any noise,
that means there is leaking somewhere inside the indoor unit. Could use soap bubble or helium detector to find
the leaking points. You must fix the leaking point before recycling. Only mount the indoor unit after the indoor unit
has passed a leak check. It will not be easy to fix the leaking, after the indoor unit is hung and connected. Better
to find and fix the leaking points before hanging and connecting it.
* Connect the inter connecting pipes to the indoor unit following general refrigeration piping practices.