Download customer and technician must read
Transcript
INSTALLATION OF INDOOR UNIT REFRIGERANT PIPING WORK WARNING: The unit must be installated and maintained by licensed HVAC Technician. SELECTION OF INSTALLATION LOCATION CAUTIONS-NOT INSTALL UNIT AT * Where cool air can be distributed throughout the room. * Where condensation water is easily drained out. * A place that can handle the weight of indoor unit. * Not in laundry, nor in exhaust area. * Where access for maintenance, is not blocked. * Where there is too much of in the area. * Where there is high levels of acid or acidity exists. * Where there is electrical supply. Select gas and liquid copper pipes per the following table. MODEL LIQOLID PIPE GAS PIPE WMMS-09EU-V2B(59) 1/4" 3/8" WMMS-12EU-V2B(59) 1/4" 1/2" WMMS-18EU-V2B(59) 1/4" 1/2" WMMS-24EU-V2B(59) 1/4" 5/8" Heat insulation layer Connecting wire Heat insulation layer Gas pipe Liquid pipe Gas pipe and liquid pipe insulation must be no less than 3/8". Pipe wrapping tape Dia. drain pipe 1/2" To keep dust and moisture out, both ends of copper pipe must be fully covered, before putting insulation on and coiling it. In field installation, must check and keep the two ends of each copper pipe fully covered, to protect against any foreign substances potentially entering the pipe and contaminating the refrigerant system. INSTALLING LOCATION OPTIONS * Ceiling * Floor (Against wall, or stand alone) * Unlock the return air grille by pressing the locking latch shown at the right. Take out optional accessories and access to wiring terminal. * Unscrew to take off the side panel. 59.0" or more 23.6" or more 23.6" or more DRAIN PIPING WORK 39.4" or more 11.8" or more (When drain hose is connected) Drain piping HANGING In the case of ceiling hanging installation, there is no need to remove hanger bracket from the indoor unit. Illustration as follows: Celling slab Buried hanging bolt Incline the drain hose BOLT POSITION INWARD * The drain pipe connection can be either on the right rear or right side. Not to be lifted * The inside diameter of the drain pipe should be equal to or slightly bigger than the outside diameter No folding of the connecting pipe. Not to be soaking in * Keep the drain pipe as short as possible and incline water downwards at a gradient of at least 1/100 to prevent air pockets. Fig.1 * Use the drain hose and clamp that come with the indoor unit. Insert the drain hose completely into the drain connector on the indoor unit. Tighten the clamp (Fig.2, 3). * Not to fold drain hose (Fig.3). *Wrap the sealing pad over the clamp and drain insulate to hose. Hanger bracket Air outlet Tighten clamp Rising Carefully pour water into drain pan Taping area Drain hose Fig.2 Fig.3 Fig.4 Check for smooth drainage after the piping work is done * Pour water into the drain pan from the air outlet to check for smooth drainage (Fig.4). YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World ! P15 OF 36 YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World ! P16 OF 36 INSTALLER'S INSTRUCTION INSTALLER'S INSTRUCTION Template In selecting pipe running path, need to avoid as many bends as possible. If it is necessary, the bending radius must be more than 1.5" or 2". Connecting indoor unit * Before connecting indoor unit, need to check if the indoor unit seals well. Dry nitrogen is loaded inside the indoor unit before being packed at factory. If you hear the nitrogen gas blasting out of the broken seal, that means the indoor unit is sealed. Otherwise, need to recharge with nitrogen and recheck. If you still don't hear any noise, that means there is leaking somewhere inside the indoor unit. Could use soap bubble or helium detector to find the leaking points. You must fix the leaking point before recycling. Only mount the indoor unit after the indoor unit has passed a leak check. It will not be easy to fix the leaking, after the indoor unit is hung and connected. Better to find and fix the leaking points before hanging and connecting it. * Connect the inter connecting pipes to the indoor unit following general refrigeration piping practices.