Download Service Manual
Transcript
SiUS121502E Troubleshooting for Outdoor Unit Troubleshooting Caution Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged. Check the power supply voltage. Is the voltage fluctuation within ±10% from the rated value? NO Correct the power supply. YES Check the connection of the compressor harness. Loose or disconnected? YES Reconnect the harness. NO Does the outdoor fan rotate smoothly? NO Replace the outdoor fan motor and the outdoor unit PCB (main PCB). YES (Precaution before turning on the power again) Make sure the power has been off for at least 30 seconds. Turn on the power. System restarted? (Repeat a few times.) YES Disturbance factors ∗ Noise ∗ Power supply distortion Check for such factors for a long term. NO Error again within 3 minutes after turning on the power? NO Replace the outdoor unit PCB (main PCB). YES Replace the indoor unit PCB (control PCB). (R20413) Service Diagnosis 139