Lubricants and their relationship with SUVA® Refrigerants
5.6.5
Draining lubricant
5.6.8
Possible entry of air
Draining lubricant is necessary:
After removing lubricant by either method, there is a danger
that air, with its associated moisture, may have entered the
compressor. Counter pressure of refrigerant coming out of
solution from the lubricant will certainly limit the entry of air,
but may not keep it out altogether.
Before starting to charge fresh lubricant, flush any air out
of the compressor by opening the suction service valve.
Quickly screw in the lubricant filler plug, then close the
valve. Most air, and air-borne moisture, will be driven out
through the lubricant filler opening.
If the compressor has been open to atmosphere for any
length of time, and particularly if solvent has been used to
flush out polymerised lubricant or sludge, pull a complete
vacuum on the compressor before charging fresh lubricant.
The purpose of this work is to get clean, moisture-free, lubricant into an uncontaminated system.
■
■
■
When changing from CFC to SUVA® Refrigerant requires
removing the major part of the Mineral Lubricant.
If the lubricant has degraded and become acid during
service.
After a burn-out: If there is any doubt that the clean-up
was not completely successful.
5.6.6
Recommended method
Equipment required:
■
■
■
■
■
■
■
■
Vacuum pump.
Connecting line.
Receptacle for lubricant to be removed: an old lubricant
container can be used, but a graduated glass flask is recommended.
A length of copper tubing: shaped, and of suitable diameter, so that when it is inserted through the lubricant filler
opening in the compressor, the end reaches bottom of the
crank-case sump.
Plastic sealing material.
Seal the connecting line , and the vacuum line, into the top
of the receptacle, using the plastic sealing material or
“mastic”.
Close both service valves to isolate the compressor.
Start the vacuum pump. By pulling a vacuum in the
receptacle, this draws the lubricant out of the compressor
into the receptacle. If, as recommended, this is a graduated glass flask, the engineer can check the quantity and
colour of the lubricant withdrawn.
5.6.7
Alternative method
Refrigerant pressure can be used instead of vacuum. The
same length of shaped copper tubing is used: however it is
sealed into the lubricant filler opening in the compressor. Sufficient refrigerant vapour is let into the compressor through
the suction service valve to create a positive pressure in the
crank-case. This causes the lubricant to flow out into the
receptacle.
This method removes the lubricant less completely than
the Recommended Method. It is more suitable for taking a
small sample of lubricant for analysis.
25