Download INSTALLATION, OPERATING and SERVICE MANUAL

Transcript
RETURN AIR AND FILTER RACK
The filter rack may be mounted on either side, the
bottom or the back of the appliance. Position the
rack so that there is easy access to change the filter.
HI/ECONO HEAT SWITCH
 This switch is provided on some models. It is
located on the front of the furnace and provides
the homeowner with the option of manually
increasing or reducing the heating power of the
furnace. It can be used to manually switch from
"Hi" to "Econo" if less heating power is
temporarily desired, depending on the outdoor
temperature.
 This switch can also be controlled automatically
by a suitable multi- or two-stage thermostat
connected to the W1 (Econo) and W2 (Hi)
terminals. Set the switch to "Econo" if a two
stage or multi-stage thermostat is used.
 If a standard thermostat is connected across W1R, a remote switch or an outdoor temperature
switch can be connected across OT-W2 to switch
from "Econo" to "Hi" as the outdoor temperature
drops. Leave the furnace switch in "Econo" if a
remote or outdoor temperature switch is used.
WARM AIR
Before installing the plenum, look into the furnace
and check the heating elements to ensure that no
damage has occurred and that they are free of
foreign material.
THERMOSTAT and ANTICIPATOR
Should be installed according to the instructions
packed with it and connected to the 24 volt terminals
on the front of the appliance. The heat anticipator
should be set to 0.4 amps.
BLOWER SPEED AND STATIC PRESSURE
The Newmac EH Electric Furnace is tested and
approved by CSA for static pressures of 0.20 to 0.50
ins wc.
The 0.20 ins wc static pressure setting is for normal
use and the units are factory equipped with the
blowers set to provide this.
The 0.50 ins wc static pressure setting is for air
conditioning. The installer should set the required
blower speed - see table below.
Set the speed of the belt-drive-blower units by
adjusting the motor pulley. Adjust this pulley to give
the recommended air temperature rise.
OT W2 W1 C
G R
2 stage Heat/Cool
Thermostat
OT W2 W1 C
Remote
Switch
(Optional)
SEQUENCE OF OPERATION
 As the room temperature drops, the thermostat
contacts will close and energize the heating
element on the first sequencer.
 After approximately 20 seconds, the first set of
contacts in the sequencer will close, bringing on
the #1 element. At the same time the circulating
blower will start.
 After approximately 40 seconds, the #2 element
will come on.
 Depending on the model, and if the furnace is set
to Hi, #3, #4, #5, and #6 elements will come on in
sequence. See below for more information on
the Hi/Econo switch setting.
 When the room thermostat is satisfied, it will
break contact. All the elements will turn off in
random sequence. The blower will stop when the
last element shuts off.
Heat/Cool
Thermostat
OT W2 W1 C
Remote
Switch
(Optional)
G R
R = 24vac
C = 24vac
G = Fan Relay
W1 = Heat Relay Stage 1
W2 = Heat Relay Stage 2
OT = (R) 24vac
G R
Heating
Thermostat
MAINTENANCE
To maintain the performance of the furnace, replace
or clean the air filter monthly.
HOMEOWNER
If you, the homeowner, suspect the furnace is not
operating properly, or if there is no heat, do not
tamper with the furnace. Have a qualified service
person check out the furnace installation.
BLOWER REMOVAL
Turn off the main electricity power supply before
servicing the furnace.
Open the centre access panel to disconnect the
wiring to the blower motor
Open the blower access panel. Carefully unscrew
the bolt(s) holding the blower assembly in place, and
remove the entire blower/motor assembly by sliding it
out through the access opening.
HI/LO CONTINUOUS FAN SWITCH
This is located on the front of the furnace and
provides the homeowner with the option of having
the circulating blower run continuously at high or low
speed. This control does not affect the normal
heating and cooling cycles of the furnace.
2