Malfunction display: High/Low pressure sensor error
Pressure sensor error
The plug
on pressure sensor is correctly
connected to the socket on
mainboard, is it?
No
Check the orientation of
plug and socket
Yes
Measure the
DC voltage value between black
line and green line of the sensor: is it
OK?(0.5~4.5V)
Yes
Replace the mainboard of outdoor
unit
135
No
Replace the pressure