Download Service Manual
Transcript
Field Setting ESiEN09-05 (5) Thermostat Control (5.1) X-control Thermo off When the DDC controller maintains level A for more than B minutes, and the thermostat is on, thermo off is carried out for at least C minutes. After C minutes, thermostat on-conditions are checked. Mode n° setting 51 Setting switch n° 8 6 9 Setting position n° 00 01 00 01 02 03 04 05 06 07 08 09 10 00 04 Setting level A = 1 (cooling) level A = 1 or 2 (cooling) B = 3 min, C = 3 min B = 5 min, C = 3 min B = 7 min, C = 3 min -B = 3 min, C = 5 min B = 5 min, C = 5 min B = 7 min, C = 5 min -B = 3 min, C = 10 min B = 5 min, C = 10 min B = 7 min, C = 10 min level A = 5 (heating) level A = 4 or 5 (heating) Thermo on When the DDC controller reaches level D or higher (lower for heating) and the thermostat is off for at least C minutes (refer to thermo off conditions), thermostat on is carried out for at least E minutes. Mode n° setting 51 Setting switch n° 7 5 b 96 Setting position n° 00 02 04 06 08 00 01 02 00 01 02 03 04 Setting D = level 1 (cooling) D = level 2 (cooling) D = level 3 (cooling) D = level 4 (cooling) D = level 5 (cooling) E = 3 min E = 5 min E = 10 min D = level 1 (heating) D = level 2 (heating) D = level 3 (heating) D = level 4 (heating) D = level 5 (heating) Test Operation