Field Setting
ESiEN09-05
(5) Thermostat Control
(5.1) X-control
„ Thermo off
When the DDC controller maintains level A for more than B minutes, and the thermostat is on,
thermo off is carried out for at least C minutes. After C minutes, thermostat on-conditions are
checked.
Mode n° setting
51
Setting switch n°
8
6
9
Setting position n°
00
01
00
01
02
03
04
05
06
07
08
09
10
00
04
Setting
level A = 1 (cooling)
level A = 1 or 2 (cooling)
B = 3 min, C = 3 min
B = 5 min, C = 3 min
B = 7 min, C = 3 min
-B = 3 min, C = 5 min
B = 5 min, C = 5 min
B = 7 min, C = 5 min
-B = 3 min, C = 10 min
B = 5 min, C = 10 min
B = 7 min, C = 10 min
level A = 5 (heating)
level A = 4 or 5 (heating)
„ Thermo on
When the DDC controller reaches level D or higher (lower for heating) and the thermostat is off
for at least C minutes (refer to thermo off conditions), thermostat on is carried out for at least E
minutes.
Mode n° setting
51
Setting switch n°
7
5
b
96
Setting position n°
00
02
04
06
08
00
01
02
00
01
02
03
04
Setting
D = level 1 (cooling)
D = level 2 (cooling)
D = level 3 (cooling)
D = level 4 (cooling)
D = level 5 (cooling)
E = 3 min
E = 5 min
E = 10 min
D = level 1 (heating)
D = level 2 (heating)
D = level 3 (heating)
D = level 4 (heating)
D = level 5 (heating)
Test Operation