ESIE07-11
Troubleshooting Chart
Compressor
overload relay
tripped or circuit
breaker trip or
fuses blown
Compressor
noisy or
vibrating
Compressor will
not load or
unload
There is low voltage during high
load condition.
1
Check the supply voltage for
excessive voltage drop.
2
There is loose power wiring.
2
Check and tighten all
connections.
3
There is a power line fault
causing unbalanced voltage.
3
Check the supply voltage.
4
There is defective or grounded
wiring in the motor.
4
Check the motor and replace if
defective.
5
There is high discharge
pressure.
5
See corrective steps for high
discharge pressure.
1
There is a compressor internal
problem.
1
Contact Daikin.
2
The oil injection is not adequate.
2
Contact Daikin.
1
The capacity control is defective.
1
See capacity control section.
2
The unloader mechanism is
defective.
2
Replace.
3
The control solenoids are
defective.
3
Replace.
1
Discharge shut-off valve is
partially closed.
1
Open the shut-off valve.
2
Non condensable is in the
system.
2
Purge the non-condensable from
the condenser coil after
shutdown.
3
Fans are not running.
3
Check the fan fuses and
electrical circuits.
4
Fan control is out of adjustment.
4
Check if the unit set-up in the
microprocessor matches the unit
model number. Check the
microprocessor condenser
pressure sensor for proper
operation.
5
Heat recovery condensers are
dirty.
5
Clean the condenser tubes by
mechanical or chemical tools.
6
System is overcharged with
refrigerant.
6
Check for excessive sub-cooling.
Remove the excess charge.
7
The condenser coil is dusty.
7
Clean the condenser coil.
8
The air recirculates from the
outlet into the unit coils.
8
Remove the cause of
recirculation.
9
Air entering the unit is restricted.
9
Remove any obstructions near
the unit.
High discharge
pressure
Part 3 – Troubleshooting
1
1
33
4
3–51
5