Operation detail
■ Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Intake Air temperature
minimum 3min
Setting Temperature .+3°C
(Compressor OFF)
A
Setting Temperature
(Compressor ON)
INDOOR FAN
1min
Hot Start
Low
Selecting
Fan Speed
B
A
minimum
minimum
minimum
10sec.
1min.
10sec.
Low
OFF
Low
Selecting fan
speed
Low
OFF
• A point;
While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed,
when it becomes lower than 40˚C fan stops.
• B point;
When the indoor Heat-Exchanger temperature is higher than 31°C, fan operates at selected fan
speed, when it becomes lower than 31°C, the fan operates at low speed for 10sec, after 10sec, it
operates at selected fan speed.
■ Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
PIPING
TEMPERATURE
25°C
1min
22°C
INDOOR FAN
COMPRESSOR
48
Indoor Unit
OFF
LOW
ON
Selected Fan