Operation detail ■ Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Intake Air temperature minimum 3min Setting Temperature .+3°C (Compressor OFF) A Setting Temperature (Compressor ON) INDOOR FAN 1min Hot Start Low Selecting Fan Speed B A minimum minimum minimum 10sec. 1min. 10sec. Low OFF Low Selecting fan speed Low OFF • A point; While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed, when it becomes lower than 40˚C fan stops. • B point; When the indoor Heat-Exchanger temperature is higher than 31°C, fan operates at selected fan speed, when it becomes lower than 31°C, the fan operates at low speed for 10sec, after 10sec, it operates at selected fan speed. ■ Hot-start Control The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C. The operation diagram is as following. PIPING TEMPERATURE 25°C 1min 22°C INDOOR FAN COMPRESSOR 48 Indoor Unit OFF LOW ON Selected Fan