Download AIR CONDITIONER
Transcript
FILE NO. SVM-09029 Table 9-4-1 Block level Check code Block Indoor P.C. board Diagnosis function Check code Air Conditioner status Symptom Condition Judgement and action Thermo. sensor short/break. Continued operation. Indicated when detected abnormal 1.Check thermo sensor. 2.If it is OK, check P.C. board. Heat exchanger sensor short/break. Continued operation. Indicated when detected abnormal 1.Check heat exchanger sensor. 2.If it is OK, check P.C. board. Indoor fan lock, abnormality of indoor fan or thermal fuse break. All off Indicated when detected abnormal 1.Check heat thermal fuse is blow or not? (Terminal block part.) 2.If the thermal fuse is not blow, check indoor fan motor. (Refer to trouble shooting flow charts.) Abnormality of other All off indoor unit P.C. board. Indicated when detected abnormal Replace P.C. borad. Cable connection/ Thermal fuse Refrigerant system 1) Wrong wiring or All off disconnection of connective cable. 2) Terminal fuse cut off. Indicated when detected abnormal 1.Check connective cable correct if wiring is wrong. 2.Check thermal fuse and Terminal blocks. 3.If it is OK, check P.C. board. Other parts (including compressor) 1) Overload relay or All off thermostat for compressor break. Indicated when detected abnormal 1.If overload relay and themostat for compressor are OK, check refrigerant cycle. 2.If refrigerant cycle is OK, check P.C. board. 3. If heat exchanger sensor is OK, check overload relay and themostat for compressor. Content detected by the check codes " " t o " " are stored in memory of the microcomputer even if the power supply is turned off. Therefore, contents of operations in the past are all displayed. – 51 −