Download continued - Lochinvar
Transcript
Service Manual 3 Troubleshooting Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface FAULT DESCRIPTION CORRECTIVE ACTION The unit has failed to prove main burner flame upon ignition. • Inspect igniter and associated wiring for damage and connection. Reference page 25 of this manual for removal and cleaning procedure. Replace if necessary. • Check for proper electrical grounding of unit. • Check incoming supply gas pressure. Refer to Section 3 - Gas Connections in the Power-fin Installation and Operation Manual for detailed information concerning the gas supply. • Verify that the tube from the gas valve to the air inlet is connected and is not damaged. • Verify that the vent/air intake pipes are correctly installed and that there are no obstructions. No Flame Ign (Will require a manual reset. Press the RESET button on the SMART SYSTEM display to reset.) • Inspect the burner. Reference page 26 of this manual for removal and cleaning procedures. Replace if necessary. • Refer to the Checking Manifold Gas Pressure and Combustion Analysis Procedure on pages 27 and 28 of this manual for the proper settings. • Check for 120 VAC to the gas valve during the ignition attempt. If no voltage is present, check the wiring between the gas valve and the main control board. • Replace the wiring or the main control board as necessary. HSI Current Low Amp draw of the hot surface igniter did not • Measure the amp draw of the hot surface igniter during (Will require a manual meet the minimum requirement of 2.6 amps. reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) Flame CKT Error 36 The main control board has detected an internal fault. the trial for ignition stage. If less than 2.6 amps replace the hot surface igniter. • If more than 2.6 amps replace the control module. • Replace the main control board.